4-6 Operation

MN2417

Table 4-2 Three/Single Phase Operation

Alternator

Voltage

Voltage at Terminal Lugs

Voltage at Plug Receptacles

Switch

Position

Alternator

Winding

Connection

Voltage

Adjust

Position

Line To Line Voltage

Line To Neutral Voltage

120VAC

Receptacles

240VAC Receptacles

(Twist Lock)

Position

Connection

Position

L1−L2

L2−L3

L1−L3

L1−N

L2−N

L3−N

L−N

L−L

L−N

Series High

Minimum

416

416

416

240

240

240

120

208

120

480/277

Series High

Wye

Middle

460

460

460

266

266

266

133

230

133

480/277

Wye

Maximum

480

480

480

277

277

277

139

240

139

Parallel Low

Minimum

208

208

208

120

120

120

120

208

120

208/120

Parallel Low

Wye

Middle

230

230

230

133

133

133

133

230

133

208/120

Wye

Maximum

240

240

240

139

139

139

139

240

139

Parallel Low

Minimum





200

100



100

100

200

100

240/120

Parallel Low

ZigZag

Middle





220

110



110

110

220

110

240/120

ZigZag

Maximum





240

120



120

120

240

120



No connection at Terminal Lug #2.

Receptacle Panel Load Connections, see Figure 4-4.

1.

240/120VAC voltage is present at the receptacle panel at all times when generator is

running.

2.

Carefully inspect all Individual load cables for broken insulation or other signs of

damage. Never use a damaged cable. Replace it before usage.

3.

Individual load cables may be routed into the receptacle compartment through the

Enclosure Electrical Access Panel.

4.

Individual load cables may be connected or disconnected while generator is running.

Use extreme care not to touch any electrical wire or terminal to avoid shock hazard.

5.

Keep Enclosure Electrical Access Panel closed at all times. This prevents rain or other

harmful elements from entering the compartment. Output metering and gauges can be

observed through the window in the Enclosure Electrical Access Panel.

Figure 4-4 Receptacle Panel (Single Phase)

Note:
Single phase power is
always available.

(GOLD)

X

(GOLD)

Y

G

W

(SILVER)

CS6369

125/250V

50A

X

Y

W

Test

Reset

CS6365N

GFI Outlet
120V, 20A

240V, 50A

Circuit Breakers (Single or Double pole)

Circuit Breakers provides protection on some
units. To reset a breaker, place it in the OFF
then the ON position.

Meters, switches, lights and other operator control components are located in various places on

each panel. Figure 4-5 can be used to identify the function and features of each operator control

regardless of where it is located on your panel.