Baldor TS250 User Manual

Page 38

Advertising
background image

4-16 Operation

MN2417

Table 4-10 Engine Setpoints

Continued

Cooling time

Runtime of the unloaded gen−set to cool the engine before stop.

Step: 1s; Range: 0 − 3600 s

AfterCoolTime

Runtime of engine after cooling pump. Binary output Cooling pump is

closed when the engine starts and opens AfterCool time delayed after

gen−set stops. Step: 1s Range: 0 − 3600s

CoolingSpeed

Selects the function of the Binary output IDLE/NOMINAL during engine

Cooling state.

NOMINAL : Cooling is executed at Nominal speed and generator

protections are active.

IDLE: Cooling is executed at Idle speed and generator protections are

switched off.

Hint: Binary output IDLE/NOMINAL must be configured and connected to

speed governor. Engine Idle speed must be adjusted on speed governor.

D+ function

ENABLED: The D+ terminal is used for both functions “running engine”

detection and charge fail detection.

CHRGFAIL: The D+ terminal is used for charge fail detection only

DISABLED: The D+ terminal is not used.

Note: Magnetization current is independent of this setpoint value.

Table 4-11 Engine Protect Setpoints

ECUFreqSelect

This setpoint should be used only for Volvo and Scania engines.

ECU Speed Adjust

This setpoint should be used only for Volvo and Scania engines.

WTBF Accept RPM

The WtBfAcceptRPM delay setpoint will start to count down since

cranking. Controller waits before communicating with the ECU for this

time. This is because the JD engine passes some erroneous RPM signals

during the first 500ms. Step: 0,1s Range: 0 − 3s

Eng prot del

During the start of the gen−set, some engine protections have to be

blocked (e.g. Oil pressure). The protections are unblocked after the

Protection del time. The time starts after reaching Start RPM.

Step: 1s; Range: 0 − 300 s

Horn timeout

Max time limit of horn sounding. Set to zero if you want to leave the output

HORN open. Step: 1s; Range: 0 − 600 s

Overspeed

Threshold for over speed protection.

Step: 1% of nominal RPM; Range: 100 − 150%

Wrn Oil press

Warning threshold level for ANALOG INPUT 1.

Step: 1 psi; Range: Sd Oil press − 10000

Sd Oil press

Shutdown threshold level for ANALOG INPUT 1.

Step: 1 psi; Range: −100 − Wrn Oil press

Oil press del

Delay for ANALOG INPUT 1. Step: 1 s; Range: 0 − 180

Sd Water temp

Warning threshold level for ANALOG INPUT 2.

Step: 1 °C; Range: Wrn Wtemp − 10000

Wrn Water temp

Warning threshold level for ANALOG INPUT 2.

Step: 1 °F; Range: Wrn Wtemp low − Sd Water temp

Wrn Wtemp low

Warning threshold level for low value on ANALOG INPUT 2.

Step: 1 °F; Range: −100 − Wrn Water temp

Water temp Low del

Delay for ANALOG INPUT 2 Wrn Wtemp low. Step: 1 s; Range:1−180 s

Water temp del

Delay for ANALOG INPUT 2 alarm. Step: 1 s; Range: 0 − 180 s

Wrn Fuel Level

Warning threshold level for ANALOG INPUT 3.

Step: 1 %; Range: Sd Fuel Level − 10000

Sd Fuel Level

Shutdown threshold level for ANALOG INPUT 3.

Step: 1 %; Range: −100 − Wrn Fuel Level

Fuel Level del

Delay for ANALOG INPUT 3. Step: 1 s; Range: 0 − 180 s

Batt overvolt

Warning threshold for high battery voltage.

Step: 0,1 V; Range: Batt undervolt − 40V

Batt undervolt

Warning threshold for low battery voltage.

Step: 0,1 V; Range: 8V − Batt overvolt

Batt volt del

Delay for low battery voltage alarm. Step: 1s; Range: 0 − 600 s

NextServTime

Counts down when engine running. If reaches zero, an alarm appears.

Step: 1h; Range: 0 −65535h