4-18 Operation

MN2417

Table 4-13 Sensor Spec Setpoints

Calibr AI1,AI2, AI3

Calibrating constant to adjust the measured value of IL analog inputs.

Physical dimension of calibrating constant is corresponding to Analog

input. Step: 1; Range: −1000 to +1000

AnOut−kW/20mA

Conversion coefficient from gen−set power to iG−IOM or PTM analog

output. Step: 1; Range: 1 to 32000

Table 4-14 IOM/PTM Module Setpoints

AnlInIOM1 lev1

The level for IOM ANALOG INPUT 1 alarm detection.

Step: 1; Range: −100 to +10000

AnlInIOM1 lev2

The level for IOM ANALOG INPUT 1 alarm detection.

Step: 1; Range: −100 to+10000

AnlInIOM1 del

Delay for IOM ANALOG INPUT 1 alarm. Step: 1 s; Range: 0 − 180 s

AnlInIOM2 lev1

The level for IOM ANALOG INPUT 2 alarm detection.

Step: 1; Range: −100 to +10000

AnlInIOM2 lev2

The level for IOM ANALOG INPUT 2 alarm detection.

Step: 1; Range: −100 to +10000

AnlInIOM2 del

Delay for IOM ANALOG INPUT 2 alarm. Step: 1 s; Range: 0 − 180 s

AnlInIOM3 lev1

The level for IOM ANALOG INPUT 3 alarm detection.

Step: 1; Range: −100 to +10000

AnlInIOM3 lev2

The level for IOM ANALOG INPUT 3 alarm detection.

Step: 1; Range: −100 to +10000

AnlInIOM3 del

Delay for IOM ANALOG INPUT 3 alarm.

Step: 1 s; Range: 0 − 180 s

AnlInIOM4 lev1

The level for IOM ANALOG INPUT 4 alarm detection.

Step: 1; Range: −100 to +10000

AnlInIOM4 lev2

The level for IOM ANALOG INPUT 4 alarm detection.

Step: 1; Range: −100 to +10000

AnlInIOM4 del

Delay for IOM ANALOG INPUT 4 alarm. Step: 1 s; Range: 0 − 180 s

The protection of IOM/PTM inputs is activated by over crossing the limits.

Calibr AInIOM 1..4

Calibrating constant to adjust the measured value of IOM/PTM analog

inputs. Physical dimension of calibrating constant is corresponding to

Analog input. Step: 1; Range: −1000 to +1000