Important, Wiring – main power, Figure 11 unit 24v thermostat connections – Bard CH4S1 User Manual

Page 15

Advertising
background image

Manual 2100-455M

Page

15 of 28

Eleven (11) wires should be run from thermostat
subbase to the 24V terminal board in the unit. An
eleven conductor, 18 gauge copper color-coded
thermostat cable is recommended. The connection
points are shown in Figure 11. An additional wire is

needed if dehumidification is used.

table 3

thermOstat WIre sIZe

ImPOrtant

Only the thermostat combinations as shown

above will work with this equipment.

transformer

Va

Fla

Wire Gauge

maximum

Distance

In Feet

65

2.3

20 gauge

45

18 gauge

60

16 gauge

100

14 gauge

160

12 gauge

250

#8403-052, 8403-053, 8403-055

Y

DH

THERMOSTAT

BARD PART #8403-060

G

L

Y1

W1/E

R

O/B

W2

A

AUX

UNIT LOW VOLTAGE

TERMINAL BLOCK

THERMOSTAT BARD PART

B

L

E

W3

W2

W1

Y1

Y2

D/YO

R

G

C

O1

W1

B

Y2

Y1

Rh

Rc

G

C

C

Factory Jumper

1

GND

MIS-2026 C

ID

GND

OD

OPTIONAL

8403-061

OUTDOOR

SENSOR

OPTIONAL

8403-062

INDOOR

SENSOR

FIGure 11

unIt 24V thermOstat cOnnectIOns

WIrInG – maIn POWer

Refer to the unit rating plate for wire sizing information
and maximum fuse or “HACR” type circuit breaker
size. Each outdoor unit is marked with a “Minimum

Circuit Ampacity”. This means that the field wiring
used must be sized to carry that amount of current.
Depending on the installed KW of electric heat, there

may be two field power circuits required. If this is the
case, the unit serial plate will so indicate. All models
are suitable only for connection with copper wire. Each
unit and/or wiring diagram will be marked “Use Copper
Conductors Only”. These instructions

must be adhered

to. Refer to the National Electrical Code (NEC) for
complete current carrying capacity data on the various
insulation grades of wiring material. All wiring must
conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75°C
copper) for all models including the most commonly

used heater sizes. Also shown are the number of field
power circuits required for the various models with
heaters.

The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR” type circuit breaker that is to
be used with the equipment. The correct size must be
used for proper circuit protection and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.

The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect. To
convert for the locking capability, bend the tab located
in the bottom left hand corner of the disconnect
opening under the disconnect access panel straight
out. This tab will now line up with the slot in the door.
When shut, a padlock may be placed through the hole
in the tab preventing entry.

See “Start Up” section for important information on
three phase scroll compressor start ups.

WIRING – LOW VOLTAGE WIRING

230 / 208V, 1 phase and 3 phase equipment have 24V
transformers with dual primary voltage. All equipment
leaves the factory wired on 240V tap. For 208V
operation, reconnect from 240V to 208V tap. The
acceptable operating voltage range for the 240 and 208V
taps are:

taP ranGe

240

253 – 216

208

220 – 187

NOTE: 460V units require no action. The voltage

should be measured at the field power

connection point in the unit and while the unit is

operating at full load (maximum amperage

operating condition).

FIGure 10

cOmmOn Wall mOuntInG InstallatIOns

Outside Wall

Closet Wall

Closet Wall

Grille

Return Air

Return Air

Supply Air

Duct

Finished Ceiling

Raised Closet Floor

Rafters

Wall Sleeve

Closet Installation

Unit (outside)

Note: duct maybe in attic or

below rafters as shown.

MIS-2240

Grille

Only needed if dehumidification is used.