sOlID state heat PumP cOntrOl

trOubleshOOtInG PrOceDure
1. NotE: A thorough understanding of the defrost

cycle sequence is essential. Review that section

earlier in this manual prior to troubleshooting the

control. Turn on AC power supply to unit.

2. Turn thermostat blower switch to “fan on” – the

indoor blower should start. (If it doesn’t,

troubleshoot indoor unit and correct problem.)

3. Turn thermostat blower to “auto” position. Indoor

blower should stop. NotE: Many models have a

1-minute blower time delay on “off” command;

wait for this to time-out.
4. Set system switch to “heat” or “cool”. Adjust

thermostat to call for heat or cool. The indoor

blower, compressor and outdoor fan should start.

NOTE: If there was no power to 24 volt transformer,

the compressor and outdoor fan motor will

not start for 5 minutes. This is because of

the compressor short cycle protection.

symptom

Description, check & Possible causes

What & how to check / repair

Compressor will not start

(heating or cooling)

1. check for leD illumination.

Is there an LED illuminated on the board (flashing)?

Yes = go to Step #2; No = go to Step #3

2. check for error codes.

Is the LED flashing a Code?

Yes = go to Step #4; No = go to Step #8

3. check for power at board.

Is there 24 volts AC between R and C?

Yes = go to Step #13; No = go to Step #9

4. check codes.

What code is blinking?

Code “1”, go to Step #6; Code “2”, go to Step#7; Fast Blink, go to Step #5

5. compressor delay active.

Wait for 5 minute delay or jump board’s “speed up pins”.

Check for proper operation; if still needed, go back to Step #1.

6. low pressure fault.

Check wiring circuit and unit pressures.

7. high pressure fault.

Check wiring circuit and unit pressures.

8. check for compressor input signal.

Is there 24 volts AC between Y and C?

Yes = go to Step #10; No = go to Step #11

9. no power to board.

The unit either does not have unit voltage, the transformer is bad or the unit wiring is

incorrect.

10. check for compressor output signal.

Is there 24 volts AC between CC & C?

Yes = go to Step #12; No = go to Step #13

11. no “Y” compressor input signal.

Check thermostat wiring, incorrect phase of unit (see section on Phase Monitor), and

finally unit wiring.

12. no “cc” compressor output signal.

Check compressor contactor for proper operation and finally check compressor.

13. Faulty board.

Replace defrost board.

Fan outdoor motor does

not run (cooling or heating

except during defrost)

Heat pump control defective

Check across fan relay on heat pump control. (Com-NC)

Replace heat pump control.

Motor defective

Check for open or shorted motor winding. Replace motor.

Motor capacitor defective

Check capacitor rating. Check for open or shorted capacitor. Replace capacitor.

Reversing valve does not

energize (heating only)

Heat pump control defective

Check for 24V between RV-C and B-C.

1. Check control circuit wiring.

2. Replace heat pump control.

Reversing valve solenoid coil defective

Check for open or shorted coil.

Replace solenoid coil.

Unit will not go into defrost

(heating only)

Temperature sensor or heat pump control defective

Disconnect temperature sensor from board and jumper across “SPEEDUP” terminals

and “SEN JMP” terminals. This should cause the unit to go through a defrost cycle within

one minute.

1. If unit goes through defrost cycle, replace temperature sensor.

2. If unit does not go through defrost cycle, replace heat pump control.

Unit will not come out of

defrost (heating only)

Temperature sensor or heat pump control defective

Jumper across “SPEEDUP” terminal.

This should cause the unit to come out of defrost within one minute.

1. If unit comes out of defrost cycle, replace temperature sensor.

2. If unit does not come out of defrost cycle, replace heat pump control.

trOubleshOOtInG

table 4

trOubleshOOtInG

LED BLINK CoDES

BLINK

FuNCtIoN

Slow

Normal function (1.0 sec on/1.0 sec off)

Fast

ASCD timer active (0.1 sec on/0.1 sec off)

1

Low pressure switch failure

2

High pressure switch failure/“Soft” Lockout

3

Defrost mode active

4

High pressure switch failure/“Hard” Lockout