Start up – Bard CH4S1 User Manual

Page 16

Advertising
background image

Manual 2100-455M

Page 16 of 28

lOW VOltaGe cOnnectIOns

These units use a grounded 24 volt AC low voltage
circuit and require at least a 2 stage heating and a 2
stage cooling thermostat.

“G” terminal is the fan input.

“Y” terminal is the compressor Stage 1 input.

“Y1” terminal is the compressor Stage 2 input.

“B” terminal is the reversing valve input. The
reversing valve must be energized for heating mode.

“R” terminal is 24 VAC hot.

“C” terminal is 24 VAC grounded.

“L” terminal is compressor lockout output. This
terminal is activated on a high or low pressure trip by
the electronic heat pump control. This is a 24 VAC
output.

“W2” terminal is second stage heat (if equipped).

“O1” terminal is the ventilation input. This terminal

energizes any factory or field installed ventilation
option.

“DH” terminal is the

dehumidifier input. This terminal

energizes the factory or field installed dehumidifier
option.

“E” terminal is the emergency heat input. This
terminal energizes the emergency heat relay if
equipped.

NOTE: For total and proper control using DDC, a

minimum of 8 controlled outputs are required

(6 if no ventilation or dehumidifier option
is installed). For proper system operation

under Emergency Heat conditions where
the compressor needs to be deactivated,
the B-W2-E outputs need to be energized.
Removing the Y (compressor) signal alone
turns the compressor off, but does not activate
the additional circuitry embedded in the heat
pump for proper and complete operation.

lOW VOltaGe cOnnectIOns

FOr DDc cOntrOl

Fan Only

Energize G

Cooling Mode 1st Stage

Energize Y, G

Cooling Mode 2nd Stage

Energize Y, Y1, G

Heat Pump Heating 1st Stage Energize Y, G, B
Heat Pump Heating 2nd Stage Energize Y, Y1, G, B

3rd Stage Heating

Energize G, W2, Y, B, Y1

w/Heat Pump (if employed)

Ventilation

Energize G, O1

Dehumidifier

Energize DH

Emergency Heat

Energize B, W2, E, G

start uP

These units require R-410A refrigerant & Polyol Ester oil.

aPPlIcatIOn:

1. Use separate service and manufacturing equipment

to avoid cross contamination of oil and refrigerants.

2. Use recovery equipment rated for R-410A

refrigerant.

3. Use manifold gauges rated for R-410A (800 psi/250

psi low).

4. R-410A is a binary blend of HFC-32 and HFC-125.

5. R-410A is nearly azeotropic - similar to R-22 and

R-12. Although nearly azeotropic, charge with

liquid refrigerant.

6. R-410A operates at 40-70% higher pressure than

R-22, and systems designed for R-22 cannot

withstand this higher pressure.

7. R-410A has an ozone depletion potential of zero,

but must be reclaimed due to its global warming

potential.

8. R-410A compressors use Polyol Ester oil.

9. Polyol Ester oil is hygroscopic; it will rapidly

absorb moisture and strongly hold this moisture in

the oil.

10. A liquid line dryer must be used - even a deep

vacuum will not separate moisture from the oil.

11. Limit atmospheric exposure to 15 minutes -

MAxIMuM.

12. If compressor removal is necessary, always plug

compressor immediately after removal. Purge

with small amount of nitrogen when inserting plugs.

Advertising
This manual is related to the following products: