Wall mount general information, Table 1 electric heat table – Bard CH4S1 User Manual

Page 4

Advertising
background image

Manual 2100-455M

Page 4 of 28

Wall mOunt General InFOrmatIOn

heat PumP Wall mOunt mODel nOmenclature

ch 4s 1 – a 05 b P X X X X

table 1

electrIc heat table

models

KW

ch3s1-a

ch3s1-b

ch3s1-c

ch4s1-a

ch5s1-a

ch4s1-a

ch5s1-a

ch4s1-a

ch5s1-a

240-1

208-1

240-3

208-3

460-3

240-1

208-1

240-3

208-3

460-3

a

btu

a

btu

a

btu

a

btu

a

btu

a

btu

a

btu

a

btu

a

btu

a

btu

4

16.7

13650

14.4

10240

5

20.8

17065

18.1

12800

20.8

17065

18.1

12800

6

14.4

20500

12.5

15360

7.2

20480

14.4

20500

12.5

15360

7.2

20480

9

21.7

30600

18.7

23030

10.8

30700

21.7

30600

18.7

23030

10.8

30700

10

41.6

34130

36.2

25600

41.6

34130

36.2

25600

15

62.5

51200

54.1

38400

36.2

51200

31.2

38400

18

51200

62.5

51200

54.1

38400

36.2

51200

31.2

38400

18

51200

18

43.3

61400

37.5

46050

21.6

61400

20

83.2

68250

72.1

51200

mODel number

cOntrOl mODules

caPacItY

3S - 3 ton

4S - 4 ton

5S - 5 ton

VOlts & Phase

A - 230/208/60/1

B - 230/208/60/3

C - 460/60/3

reVIsIOns

KW

VentIlatIOn OPtIOns

B - Blank-off Plate

R - Energy Recovery

V - Commercial Ventilator -

Motorized with Exhaust

FIlter OPtIOns

P - 2-Inch Pleated

cOlOr OPtIOns

X - Beige (Standard)

4 - Buckeye Gray

5 - Desert Brown

8 - Dark Bronze

cOIl OPtIOns

X - Standard

Outlet OPtIOns

X - Front (Standard)

T - Top Outlet

Advertising