Bryant

11

2.5

MANUAL TRANSFER OPERATION

2.5.1 TRANSFER TO GENERATOR

POWER SOURCE

To start the generator and activate the transfer switch

manually, proceed as follows:
1. Set the generator’s AUTO/OFF/MANUAL switch

to OFF.

2. Set the generator’s main circuit breaker to its OFF (or

open) position.

3. Turn OFF the utility power supply to the transfer

switch using the means provided (such as a

utility main line circuit breaker).

Do not attempt to activate the transfer switch
manually until all power voltage supplies to
the switch have been positively turned off.
Failure to turn off all power voltage supplies
may result in extremely hazardous and possibly
fatal electrical shock.

4. Use the manual transfer handle inside the transfer

switch to move the main contacts to their “Standby”

position, i.e., loads connected to the standby power

source (Figure 2.2).

Figure 2.2 – Manual Transfer Switch Operation

5. To crank and start the engine, set the

AUTO/OFF/MANUAL switch to MANUAL.

6. Let the engine stabilize and warm up for a few

minutes.

7. Set the generator’s main circuit breaker to its ON (or

closed) position. The standby power source now

powers the loads.

2.5.2 TRANSFER BACK TO UTILITY POWER

SOURCE

When utility power has been restored, transfer back to

that source and shut down the generator. This can be

accomplished as follows:
1. Set the generator’s main circuit breaker to its OFF (or

open) position.

2. Let the engine run for a minute or two at no-load to

stabilize the internal temperatures.

3. Set the generator’s AUTO/OFF/MANUAL switch to

its OFF (or open) position. The engine should

shut down.

4. Check that utility power supply to the transfer switch

is turned OFF.

Do not attempt to activate the transfer switch
manually until all power voltage supplies
to the switch have been positively turned off.
Failure to turn off all power voltage supplies
may result in extremely hazardous and possibly
fatal electrical shock.

5. Use the manual transfer handle inside the transfer

switch to move the main contacts back to their

UTILITY position, i.e., loads connected to the utility

power source (Figure 2.2).

6. Turn ON the utility power supply to the transfer

switch using the means provided.

7. Set the system to automatic operation as outlined in

“Automatic Transfer Operation,” Section 2.3.

2.6

SETTING THE EXERCISE TIMER

This generator is equipped with an exercise timer. Once

it is set, the generator will start and exercise once every

seven days, on the day of the week and at the time of day

the following sequence is completed. During this

exercise period, the unit runs for approximately 12

minutes and then shuts down. Transfer of loads to the

generator output does not occur during the exercise

cycle.
A switch on the control panel (see Figure 2.1) permits

selection of the day and time for the system to exercise.

At the chosen time, perform the following sequence to

select the desired day and time of day the system will

exercise.
1. Verify that the AUTO/OFF/MANUAL switch is set

to AUTO.

2. Hold down the “Set Exercise Time” switch until the

generator starts (approximately 10 seconds) and

then release.

3. The generator will start and run for approximately 12

minutes and then shut down on its own. The

exerciser will then be set to run at that time of day

every week.

DANGER

‹

DANGER

‹

Section 2 — Operation