6 system set led, 7 fuel requirements and recommendations, 8 fuel consumption – Bryant ASPAS1BBA012 User Manual

Page 9: 9 location, Danger

Advertising
background image

Bryant

7

1.6

SYSTEM SET LED

The “System Set” LED is lit when all of the following

conditions are true:
1. The AUTO/OFF/MANUAL switch is set to the AUTO

position.

2. The utility voltage being supplied to the unit is being

sensed by the PCB. If the utility sense voltage is not

connected to the unit or if it is below 168 volts AC,

then the system set light will flash rapidly. This

indicates that if the AUTO/OFF/ MANUAL switch is

placed in the Auto position, the generator will start.

3. The “Not In Auto” dip switch is set to the OFF position

on the control board.

4. No alarms are present, for example, low oil pressure,

high temperature, etc.

1.7

FUEL REQUIREMENTS
AND RECOMMENDATIONS

With LP gas, use only the vapor withdrawal

system. This type of system uses the vapors formed

above the liquid fuel in the storage tank.
The engine has been fitted with a fuel carburetion system

that meets the specifications of the 1997 California Air

Resources Board for tamper-proof dual fuel systems.

The unit will run on natural gas or LP gas, but it has been

factory set to run on natural gas. Should the primary fuel

need to be changed to LP gas, the fuel system needs to

be reconfigured. See Section 1.9 for instructions on

reconfiguration of the fuel system.
Recommended fuels should have a Btu content of at

least 1,000 Btus per cubic foot for natural gas; or at least

2,520 Btus per cubic foot for LP gas. Ask the fuel supplier

for the Btu content of the fuel.
Required fuel pressure for natural gas is 5 inches to 7

inches water colum (0.18 to 0.25 psi); and for liquid

propane, 11 inches to 14 inches of water column (0.4

to 0.5 psi).

NOTE:

Any piping used to connect the generator to the fuel

supply should be of adequate size to ensure the fuel

pressure NEVER drops below 4 inches water colum

for natural gas or 10 inches water column for liquid

propane for all load ranges.

1.8

FUEL CONSUMPTION

*Natural gas is in cubic feet per hour.

**LP is in gallons per hour/cubic feet per hour.

*** Values given are approximate.

Gaseous fuels such as natural gas and liquid
propane (LP) gas are highly explosive. Even the
slightest spark can ignite such fuels and cause
an explosion. No leakage of fuel is permitted.
Natural gas, which is lighter than air, tends to
collect in high areas. LP gas is heavier than air
and tends to settle in low areas.

1.9

LOCATION

1.9.1 GENERATOR

Install the generator set, in its protective enclosure,

outdoors, where adequate cooling and ventilating air is

always available. Consider these factors:
• Install the unit where air inlet and outlet openings will

not become obstructed by leaves, grass, snow, etc. If

prevailing winds will cause blowing or drifting, consider

using a windbreak to protect the unit.

• Install the generator on high ground where water

levels will not rise and endanger it.

• Allow sufficient room on all sides of the generator for

maintenance and servicing. A good rule is to allow

three feet of space on all sides.

• Where strong prevailing winds blow from one direction,

face the generator air inlet openings to the prevailing

winds.

• Install the generator as close as possible to the fuel

supply, to reduce the length of piping.

• Install the generator as close as possible to the

transfer switch. HOWEVER, REMEMBER THAT

LAWS OR CODES MAY REGULATE THE

DISTANCE.

The genset must be installed on a level surface. The

base frame must be level within two (2) inches all around.

1.9.2 TRANSFER SWITCH

1.9.2.1 7 kW, 12 kW and 15 kW Units

The transfer switch shipped with this generator is

enclosed in a NEMA 1 enclosure. This type of

enclosure is intended for indoor use only. Follow

these rules:
• Install the transfer switch indoors on a firm, sturdy

supporting structure.

• To prevent switch distortion, level the switch if

necessary. This can be done by placing washers

between the switch enclosure and mounting surface.

• Never install the switch where water or any corrosive

substance might drip onto the enclosure.

• Protect the switch at all times against excessive

moisture, dust, dirt, lint, construction grit and corrosive

vapors.

DANGER

Section 1 — General Information

Bryant Air-cooled 7 kW, 12 kW and 15 kW Generators

Model #

Nat. Gas (*)

LP Vapor (**)

1/2 Load

Full Load

1/2 Load

Full Load

6/7 kW

66

119

0.82/30

1.47/54

12 kW

152

215

1.53/56

2.08/76

13/15 kW

156

220

1.58/58

2.40/88

Advertising
This manual is related to the following products: