1 unpacking/inspection, 2 protection systems, Danger – Bryant ASPAS1BBA012 User Manual

Page 6

Advertising
background image

Only qualified electricians or contractors should
attempt such installations, which must comply
strictly with applicable codes, standards and
regulations.

1.1

UNPACKING/INSPECTION

After unpacking, carefully inspect the contents

for damage.
• This standby generator set has been factory supplied

with a weather protective enclosure that is intended for

outdoor installation only.

• This UL listed standby generator set is packaged with

an automatic transfer switch with built in load center.

The combination transfer switch and load center is

pre-wired with a two foot and 30 foot conduit. Circuit

breakers for emergency circuit connections are

included.

• This UL listed, 2-pole switch is rated at 100 AC

amperes at 250 volts maximum. This transfer switch

is for indoor use only.

If this generator is used to power electrical load
circuits normally powered by a utility power
source, it is required by code to install a
transfer switch. The transfer switch must
effectively isolate the electrical system from the
utility distribution system when the generator
is operating (NEC 700, 701 & 702). Failure to
isolate an electrical system by such means will
result in damage to the generator and also may
result in injury or death to utility power
workers due to backfeed of electrical energy.

If any loss or damage is noted at time of delivery, have

the person(s) making the delivery note all damage on the

freight bill or affix their signature under the consignor's

memo of loss or damage.
If a loss or damage is noted after delivery, separate the

damaged materials and contact the Bryant for claim

procedures.
“Concealed damage” is understood to mean damage to

the contents of a package that is not in evidence at the

time of delivery, but is discovered later.

1.2

PROTECTION SYSTEMS

Unlike an automobile engine, the generator may have to

run for long periods of time with no operator present to

monitor engine conditions. For that reason, the engine is

equipped with the following systems that protect it

against potentially damaging conditions:
1. Low Oil Pressure Sensor

3. Overcrank

2. High Temperature Sensor

4. Overspeed

There are LED readouts on the control panel to notify

personnel that one of these faults has occurred. There is

also a “System Set” LED that is lit when all of the

conditions describe in Section 1.3 are true.

1.3

NEC REQUIREMENT FOR ARC
FAULT CIRCUIT INTERRUPTION
BREAKER FOR BEDROOMS

In 2001, the National Electric Code (NEC) introduced a

requirement for new construction. This new requirement

indicates the need for Arc Fault Circuit Interrupters to be

used to protect the complete branch circuit that feeds a

dwelling bedroom. The actual NEC requirement is

indicated below.

1.3.1 SECTION 210.12 ARC FAULT CIRCUIT

INTERRUPTER PROTECTION

1. Definition: An arc fault circuit interrupter is a device

intended to provide protection from the effects of arc

faults by recognizing characteristics unique to arcing

and by functioning to de-energize the circuit when an

arc fault is detected.

2. Dwelling Unit Bedrooms: All branch circuits that

supply 125 volt, single-phase, 15 and 20 ampere

outlets installed in dwelling unit bedrooms shall be

protected by an arc fault circuit interrupter listed to

provide protection of the entire branch circuit.

Section 210.12 requires that AFCI protection be provided

on branch circuits that supply outlets (receptacle,

lighting, etc.) in dwelling bedrooms. The requirement is

limited to 15 and 20 ampere, 125 volt circuits. There is no

prohibition against providing AFCI protection on other

circuits or in locations other than bedrooms. Because

circuits are often shared between a bedroom and other

areas such as closets and hallways, providing AFCI

protection on the complete circuit would comply with

210.12.
If during the installation of the Bryant Home Standby

system the decision is made to provide back up power to

a bedroom branch circuit, then the circuit breaker in the

Bryant Transfer Switch should be replaced with an Arc

Fault Circuit Interrupter.
It is most important that breakers only be switched like for

like. For instance, if replacing a 15A breaker, it MUST be

replaced with a 15A AFCI breaker. Likewise, a 20A

breaker MUST be replaced with a 20A AFCI.
These AFCI breakers are available at the nearest

electrical wholesaler or hardware store.
Siemens Item #

Description

Q115AF

15A Single Pole AFCI

Q120AF

20A Single Pole AFCI

‹

!

DANGER

Section 1 — General Information

Bryant Air-cooled 7 kW, 12 kW and 15 kW Generators

4

Bryant

Advertising
This manual is related to the following products: