9 corrosion protection, 10 attention after submersion, 11 out of service procedure – Bryant ASPAS1BBA012 User Manual

Page 18

Advertising
background image

16 Bryant

Figure 3.8 – Cooling Vent Locations

The exhaust from this product gets extremely
hot and remains hot after shutdown. High
grass, weeds, brush, leaves, etc. must remain
clear of the exhaust. Such materials may ignite
and burn from the heat of the exhaust system.

The maximum ambient temperature for the
generator is 40° C (104° F).

3.9

CORROSION PROTECTION

Periodically wash and wax the enclosure using

automotive type products. Frequent washing is

recommended in salt water/coastal areas. Periodically

spray all engine linkage parts and brackets with corrosion

inhibiting spray such as WD-40 or a comparable product.

3.10 ATTENTION AFTER SUBMERSION

If the generator has been submerged in water,

it must not be started and operated. Following any

submersion in water, have a Bryant Dealer thoroughly

clean and dry the generator.

3.11 OUT OF SERVICE PROCEDURE

3.11.1 REMOVAL FROM SERVICE

If the generator cannot be exercised every seven days,

and will be out of service longer than 90 days, prepare

the generator for storage as follows:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line and

allow the unit to shut down.

3. Once the unit has shut down, it will signal a low oil

fault.

4. Set the generator’s main circuit breaker to its OFF (or

open) position.

5. Set the AUTO/OFF/MANUAL switch to OFF and turn

off the utility power to the transfer switch. Remove

the 7.5A and 15A fuses from the generator control

panel. Disconnect the battery cables as outlined in

“General Hazards” (page 2). Turn on the utility power

supply to the transfer switch in order to power the

emergency load centers circuits while utility power is

available.

6. While the engine is still warm from running, drain the

oil completely. Refill the crankcase with oil. See

”Engine Oil Recommendations,” Section 3.3.1.

7. Attach a tag to the engine indicating the viscosity and

classification of the oil in the crankcase.

8. Remove the spark plug(s) and spray fogging agent

into the spark plug(s) threaded openings. Reinstall

and tighten the spark plug(s).

9. Remove the battery and store it in a cool, dry room

on a wooden board. Never store the battery on any

concrete or earthen floor.

10. Clean and wipe the entire generator.

3.11.2 RETURN TO SERVICE

To return the unit to service after storage, proceed

as follows:
1. Verify that utility power is turned off and that the

AUTO/OFF/MANUAL switch is set to OFF.

2. Check the tag on the engine for oil viscosity and

classification. Verify that the correct recommended

oil is used in the engine (see Section 3.3.1). If

necessary, drain and refill with the proper oil.

3. Check the state of the battery. Fill all cells of

unsealed batteries to the proper level with distilled

water. DO NOT USE TAP WATER IN THE

BATTERY. Recharge the battery to 100 percent

state of charge, or, if defective, replace the battery.

See “Specifications,” Section 1.5, for type and size.

4. Clean and wipe the entire generator.
5. Remove the 7.5A and 15A fuses from the generator

control panel. Reconnect the battery. Observe

battery polarity. Damage may occur if the battery is

connected incorrectly.

6. Open the fuel shutoff valve.
7. Insert the 7.5A and 15A fuses into the generator

control panel. Start the unit by moving the

AUTO/OFF/MANUAL switch to MANUAL. Allow the

unit to warm up thoroughly.

8. Stop the unit by setting the AUTO/OFF/MANUAL

switch to OFF.

9. Turn on the utility power to the transfer switch.
10. Set the AUTO/OFF/MANUAL switch to AUTO.
11. The generator is now ready for service.

NOTE:

If the battery was dead or disconnected, the exercise

timer must be reset.

‹

‹

!

Section 3 — Maintenance

Bryant Air-cooled 7 kW, 12 kW and 15 kW Generators

MAINTENENANCE

Advertising
This manual is related to the following products: