7 protection systems, 1 fuses – Bryant ASPAS1BBA012 User Manual

Page 14

Advertising
background image

12 Bryant

NOTE:

The exerciser will only work in the AUTO mode and

will not work unless this procedure is performed. The

exerciser will need to be reset every time the 12-volt

battery is disconnected and then reconnected.

The exerciser WILL NOT work if dip switch 2 on
the controller printed circuit board (Remote Not
Auto) is ON.

NOTE:

Damage will result if battery connections are made in

reverse.

2.7

PROTECTION SYSTEMS

2.7.1

LOW OIL PRESSURE SWITCH

This switch (Figure 2.3) has normally closed contacts

that are held open by engine oil pressure during cranking

and operating. Should oil pressure drop below the 8 psi

limit, switch contacts close, and the engine shuts down.

The Low Oil LED will light. The unit should not be

restarted until oil is added. The AUTO/OFF/MANUAL

switch must then be turned to OFF and then back to

AUTO to reset.

2.7.2

HIGH TEMPERATURE SWITCH

This switch’s contacts (Figure 3.3) close if the

temperature should exceed approximately 140º C (284º

F), initiating an engine shutdown. The High Temp. LED

will light. The generator will automatically restart and the

LED on the generator control panel will reset once the

temperature has returned to a safe operating level.

Figure 2.3 – Low Oil Pressure and

High Temperature Switches

2.7.3

OVER CRANK

This feature prevents the generator from damaging itself

when it continually attempts to start and another problem,

such as no fuel supply, prevents it from starting. The unit

will crank and rest for a preset time limit. Then, it will stop

cranking, and the Over Crank LED on the generator

control panel will light indicating an over crank failure.

The AUTO/OFF/MANUAL switch will need to be set to

OFF and then back to AUTO to reset the generator

control board.

NOTE:

If the fault is not repaired, the over crank feature will

continue to activate.

2.7.3.1 Approximate Crank Cycle Times

• 15 seconds ON
• 7 seconds OFF
• 7 seconds ON
• 7 seconds OFF
• Repeat for 45 seconds

Approximately 90 seconds total

2.7.4

OVER SPEED

This feature protects the generator from damage by

shutting it down if it happens to run faster than the preset

limit. This protection also prevents the generator from

supplying an output that could potentially damage

appliances connected to the generator

circuit. If this protective shutdown should occur the Over

Speed LED will light. Contact the nearest Bryant Dealer

if this failure occurs.

3.1

FUSES

The generator panel's 15-amp fuse (Figure 2.1) protects

the DC control circuit and the battery charge circuit

against overload. This fuse is wired in series with the

battery output lead to the panel. If this fuse element has

melted open, the engine will not be able to crank or start.

The generator will also lose all battery charge

capabilities. Replace this fuse using only an identical 15-

amp replacement fuse. To replace the fuse, push the

fuse holder cap down and rotate it counterclockwise.
The generator panel's 7.5-amp fuse protects the 12 VDC

accessory socket. If the fuse element has melted open,

the 12 VDC socket will not be able to provide power to

any accessories. Replace this fuse using only an

identical 7.5-amp replacement fuse. To replace the fuse,

push the fuse holder cap down and rotate it

counterclockwise.

‹

‹

Oil Filter

Oil
Drain
Hose

Low Oil Switch

High Temp Switch

Loose

n

‹

‹

!

Section 2 — Operation

Bryant Air-cooled 7 kW, 12 kW and 15 kW Generators

Advertising
This manual is related to the following products: