PERFORMANCE DATA (cont)

NET COOLING CAPACITIES (cont)

583A--036

Temp (F)

Air Ent

Condenser

Evaporator Air — Cfm/BF

1050/0.111

1200/0.142

1350/0.181

Evaporator Air — Ewb (F)

62

67

72

62

67

72

62

67

72

85

TC

31.4

36.2

40.6

32.4

37.1

41.2

33.1

37.6

41.5

SHC

28.7

24.4

19.7

30.9

26.0

20.4

33.1

27.3

20.9

kW

2.82

2.88

2.93

2.93

3.01

3.06

3.03

3.16

3.20

95

TC

30.0

34.3

39.0

30.7

35.0

39.6

31.7

35.7

39.9

SHC

28.0

23.7

19.2

30.1

25.2

19.9

31.7

26.7

20.5

kW

3.12

3.21

3.26

3.22

3.37

3.38

3.34

3.48

3.53

105

TC

28.6

32.6

37.3

29.4

33.4

37.9

30.4

34.0

38.2

SHC

27.3

23.1

18.6

29.4

24.7

19.4

30.4

26.1

20.0

kW

3.45

3.56

3.60

3.53

3.68

3.73

3.67

3.83

3.88

115

TC

27.0

30.8

35.7

28.2

31.5

36.2

29.1

32.0

36.4

SHC

26.4

22.4

18.0

28.2

23.9

18.8

29.1

25.4

19.4

kW

3.77

3.93

3.97

3.87

4.06

4.11

4.03

4.20

4.26

125

TC

25.5

29.0

33.9

26.7

29.4

34.4

27.8

29.8

34.6

SHC

25.5

21.7

17.4

26.7

23.2

18.2

27.8

24.6

18.8

kW

4.09

4.29

4.37

4.22

4.44

4.50

4.40

4.58

4.65

583A--042

Temp (F)

Air Ent

Condenser

Evaporator Air — Cfm/BF

1225/0.057

1400/0.075

1575/0.099

Evaporator Air — Ewb (F)

62

67

72

62

67

72

62

67

72

85

TC

39.2

42.9

46.1

39.8

43.3

46.3

40.2

43.3

46.2

SHC

35.4

29.5

23.4

37.4

30.7

23.8

39.1

31.6

24.0

kW

3.81

3.82

3.79

3.93

3.97

3.93

4.06

4.15

4.09

95

TC

37.6

41.6

44.9

38.3

42.0

45.1

38.7

42.0

45.1

SHC

34.4

29.0

23.0

36.6

30.3

23.5

38.7

31.3

23.8

kW

3.80

3.82

3.80

3.91

4.04

3.94

4.03

4.16

4.11

105

TC

35.9

40.0

43.6

36.6

40.3

43.7

37.3

40.3

43.6

SHC

33.6

28.4

22.5

35.6

29.7

23.0

37.3

30.8

23.4

kW

3.79

3.83

3.80

3.89

3.98

3.95

3.99

4.17

4.12

115

TC

34.2

38.2

42.0

34.9

38.5

42.1

35.8

38.5

42.0

SHC

32.7

27.7

21.9

34.9

29.1

22.5

35.8

30.2

22.9

kW

3.77

3.83

3.81

3.86

3.99

3.95

3.93

4.18

4.13

125

TC

32.5

36.4

40.1

33.5

36.6

40.2

34.3

36.6

40.1

SHC

31.8

26.9

21.2

33.5

28.3

21.8

34.3

29.4

22.2

kW

3.75

3.83

3.81

3.82

3.99

3.95

3.91

4.18

4.13

LEGEND

BF

Bypass Factor

Ewb — Entering Wet-Bulb
kW

Total Unit Power Input

SHC — Sensible Heat Capacity (1000 Btuh)
TC

Total Capacity (1000 Btuh) (net)

NOTES:
1. Ratings are net; they account for the effects of the evaporator-fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:

sensible capacity (Btuh)

t

= t

ldb

edb

1.10 x cfm

t

= Wet-bulb temperature corresponding to enthalpy of air leaving

lwb

evaporator coil (h

)

lwb

total capacity (Btuh)

h

= h

lwb

ewb

4.5 x cfm

Where: h

= Enthalpy of air entering evaporator coil

ewb

4. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 − BF) x (edb − 80).