Bryant 583A User Manual

Page 8

Advertising
background image

BASE UNIT DIMENSIONS — UNIT SIZES 024-036

REQ’D CLEARANCES FOR OPERATION AND SERVICING. in. (mm)

Evaporator coil access side . . . . . . . . . . . . . . . . . . . . 36 (914)
Power entry side (except for NEC requirements)

. . . . . . . . . . 36 (914)

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 (1219)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . 12 (304.8)*

*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall system,

then the system performance may be compromised.

REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)

Top of unit . . . . . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . 2 (50.8)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . 0.50 (12.7)
Flue panel . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914.4)

NEC REQ’D CLEARANCES. in. (mm)

Between units, power entry side

. . . . . . . . . . . . . . 42 (1066.8)

Unit and ungrounded surfaces, power entry side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side

. . . . . . . . . . . . . . . . . 42 (1066.8)

UNIT
583A

ELECTRICAL

CHARACTERISTICS

UNIT WEIGHT

UNIT HEIGHT

in. [mm]

‘‘A’’

CENTER OF GRAVITY

in. [mm]

lb

kg

X

Y

Z

024040/060

208/230-1-60

290.0

639.3

35.02 [889.5]

22.0 [558.8]

14.5 [368.3]

16.0 [406.4]

030040/060

208/230-1-60, 208/230-3-60

313.0

690.0

39.02 [991.1]

22.0 [558.8]

15.3 [387.4]

17.6 [447.0]

036060/090

208/230-1-60, 208/230-3-60, 460-3-60

321.0

707.7

35.02 [889.5]

22.0 [558.8]

15.3 [387.4]

16.5 [419.1]

LEGEND

CG

Center of Gravity

COND

Condenser

EVAP

Evaporator

NEC

National Electrical Code

REQ’D — Required

NOTE: Dimensions are in mm [in.].