PERFORMANCE DATA (cont)

NET COOLING CAPACITIES (cont)

583A--048

Temp (F)

Air Ent

Condenser

Evaporator Air — Cfm/BF

1400/0.050

1600/0.085

1800/0.119

Evaporator Air — Ewb (F)

62

67

72

62

67

72

62

67

72

85

TC

45.2

49.7

54.7

46.4

50.9

56.0

47.5

51.9

57.1

SHC

41.4

34.6

27.6

44.6

37.2

29.2

47.5

39.6

30.8

kW

4.04

4.08

4.12

4.05

4.09

4.13

4.06

4.10

4.14

95

TC

43.5

47.8

52.5

44.6

48.0

53.7

45.7

49.8

54.6

SHC

40.4

33.7

26.7

43.4

34.9

28.3

45.7

38.6

29.8

kW

4.45

4.50

4.55

4.46

4.62

4.56

4.47

4.53

4.58

105

TC

41.3

45.4

49.8

42.3

46.4

50.9

43.4

47.2

51.7

SHC

39.0

32.5

25.6

41.6

34.9

27.1

43.4

37.2

28.6

kW

4.91

4.95

5.00

4.93

4.97

5.02

4.93

4.98

5.03

115

TC

37.6

42.4

46.4

39.0

43.3

47.5

40.6

44.0

48.3

SHC

35.4

30.9

24.1

38.3

32.9

25.6

40.6

35.0

27.0

kW

5.39

5.46

5.51

5.41

5.48

5.43

5.44

5.49

5.55

125

TC

33.9

36.1

42.5

35.8

37.8

43.4

37.4

38.8

44.1

SHC

27.8

25.5

22.1

33.7

28.0

23.4

37.4

30.1

24.6

kW

6.30

5.94

6.05

6.18

5.97

6.06

6.15

5.98

6.08

583A--060

Temp (F)

Air Ent

Condenser

Evaporator Air — Cfm/BF

1750/0.082

2000/0.130

2250/0.162

Evaporator Air — Ewb (F)

62

67

72

62

67

72

62

67

72

85

TC

55.2

60.9

66.4

56.1

61.5

66.4

56.6

61.6

66.9

SHC

49.9

42.1

33.8

53.2

44.3

33.9

55.9

46.3

35.3

kW

4.92

4.97

5.00

5.14

5.23

5.28

5.41

5.55

5.59

95

TC

52.2

58.0

63.7

53.2

58.5

64.1

53.9

58.4

64.0

SHC

48.2

41.0

32.7

51.8

43.2

33.6

53.9

44.8

34.2

kW

5.39

5.57

5.50

5.64

5.75

5.77

5.90

6.03

6.09

105

TC

49.1

54.4

60.4

49.9

54.9

60.7

50.9

55.0

60.5

SHC

47.3

39.4

31.5

49.9

41.6

32.4

50.9

43.5

33.0

kW

5.87

5.98

6.02

6.13

6.22

6.30

6.34

6.57

6.62

115

TC

45.9

50.2

55.2

46.8

50.3

55.5

47.3

50.2

55.3

SHC

45.3

37.4

29.4

46.8

39.4

29.8

47.3

41.0

30.8

kW

6.39

6.48

6.54

6.57

6.75

6.81

6.85

7.07

7.14

125

TC

42.5

46.5

50.6

43.7

46.9

50.6

44.9

46.2

50.2

SHC

42.5

36.1

27.3

43.7

38.4

28.2

44.9

39.5

28.6

kW

7.03

7.13

7.13

7.22

7.38

7.40

7.51

7.67

7.72

LEGEND

BF

Bypass Factor

Ewb — Entering Wet-Bulb
kW

Total Unit Power Input

SHC — Sensible Heat Capacity (1000 Btuh)
TC

Total Capacity (1000 Btuh) (net)

NOTES:
1. Ratings are net; they account for the effects of the evaporator-fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:

sensible capacity (Btuh)

t

= t

ldb

edb

1.10 x cfm

t

= Wet-bulb temperature corresponding to enthalpy of air leaving

lwb

evaporator coil (h

)

lwb

total capacity (Btuh)

h

= h

lwb

ewb

4.5 x cfm

Where: h

= Enthalpy of air entering evaporator coil

ewb

4. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 − BF) x (edb − 80).