PERFORMANCE DATA (cont)

HIGH ALTITUDE COMPENSATION

NATURAL GAS ONLY

ORIFICE CONVERSION — 3.5 in. wg MANIFOLD PRESSURE*

ALTITUDE (ft)

INPUT
(Btuh)

OUTPUT

(Btuh)

ORIFICE

NUMBER†

0-2000

40,000

32,040

#44

60,000

47,040

#38

90,000

71,910

#38

115,000

93,265

#33

130,000

104,390

#31

2001-4500

33,290

27,130

#49

49,930

40,690

#43

74,900

61,040

#43

95,700

78,000

#38

108,180

88,170

#36

4501-6000

31,310

25,520

#50

46,970

38,280

#44

70,450

57,420

#44

90,020

73,370

#40

101,760

82,930

#37

*As the height above sea level increases, there is less oxygen per cubic ft of air.

Therefore heat input rate should be reduced at higher altitudes.

†Orifices available through your distributor.

LIQUID PROPANE ONLY

ORIFICE CONVERSION — 3.5 in. wg MANIFOLD PRESSURE*

ALTITUDE (ft)

INPUT
(Btuh)

OUTPUT

(Btuh)

ORIFICE

NUMBER†

0-2000

40,000

33,200

#50

57,000

47,310

#46

85,500

70,965

#46

115,000

95,450

#42

127,000

105,410

#41

2001-4500

33,290

27,630

#53

47,430

39,370

#50

71,150

59,050

#50

95,700

79,430

#45

105,690

87,720

#44

4501-6000

31,310

25,990

NOT TO BE USED

ABOVE 4500 FT

44,620

37,030

#51

66,930

55,550

#51

90,020

74,720

#47

99,140

82,510

#45

*As the height above sea level increases, there is less oxygen per cubic ft of air.

Therefore, heat input rate should be reduced at higher altitudes.

†Orifices available through your distributor.