BASE UNIT DIMENSIONS — UNIT SIZES 042-060

REQ’D CLEARANCES FOR OPERATION AND SERVICING. in. (mm)

Evaporator coil access side . . . . . . . . . . . . . . . . . . 36 (914)
Power entry side (except for NEC requirements) . . . . . . . . . 36 (914)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . 48 (1219)
Side opposite ducts

. . . . . . . . . . . . . . . . . . . . . 36 (914)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . 12 (304.8)*

*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall

system, then the system performance may be compromised.

REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)

Top of unit . . . . . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . 2 (50.8)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . 0.50 (12.7)
Flue panel . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914.4)

NEC REQ’D CLEARANCES. in. (mm)

Between units, power entry side

. . . . . . . . . . . . . . 42 (1066.8)

Unit and ungrounded surfaces, power entry side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side

. . . . . . . . . . . . . . . . . 42 (1066.8)

UNIT
583A

ELECTRICAL

CHARACTERISTICS

UNIT WEIGHT

UNIT HEIGHT

in. [mm]

‘‘A’’

CENTER OF GRAVITY

in. [mm]

lb

kg

X

Y

Z

042060/090

208/230-1-60, 208/230-3-60, 460-3-60

382

842.2

38.98 [ 990.2]

23.0 [584.2]

16.3 [412.8]

16.6 [421.6]

048090/115/130

208/230-1-60, 208/230-3-60, 460-3-60

421

928.2

38.98 [ 990.2]

21.5 [546.1]

16.6 [422.1]

18.0 [457.2]

060090/115/130

208/230-1-60, 208/230-3-60, 460-3-60

468

1031.7

42.98 [1091.7]

23.5 [596.9]

16.3 [412.8]

17.6 [447.0]

LEGEND

CG

Center of Gravity

COND

Condenser

EVAP

Evaporator

NEC

National Electrical Code

REQ’D — Required

NOTE: Dimensions are in mm [in.]