GUIDE SPECIFICATIONS (cont)

L. Motors:

1. Compressor motors shall be of the refrigerant-cooled

type with line-break thermal and current overload
protection.

2. All fan motors shall have permanently lubricated bear-

ings, and inherent, automatic reset, thermal overload
protection.

3. Condenser-fan motor shall be totally enclosed.

M. Special Features:

1. Louvered Grille:

Wire grille shall be standard on all units. Louvered
grille shall be available as a factory-installed option to
provide hail guard and vandalism protection.

2. Coil Options:

Shall include factory-installed optional copper/copper
and vinyl-coated refrigerant coils.

3. Economizer:

a.

Economizer controls capable of providing free
cooling using outside air.

b.

Equipped with low leakage dampers not to
exceed 3% leakage, at 1.0 in. wg pressure
differential.

c.

Spring return motor shuts off outdoor damper on
power failure.

4. Flat Roof Curb:

Curbs shall have seal strip and a wood nailer for flash-
ing

and

shall

be

installed

per

manufacturer’s

instructions.

5. Manual Outdoor Air Damper:

Package shall consist of damper, birdscreen, and rain-
hood which can be preset to admit outdoor air for
year-round ventilation.

6. Thermostat:

To provide for one-stage heating and cooling in addi-
tion manual or automatic changeover and indoor fan
control.

7. Natural-to-Propane Conversion Kit:

Shall be complete with all required hardware to con-
vert to liquid propane (LP) operation at 3.5 in. wg
manifold pressure.

8. Low Ambient Package:

Shall consist of a solid-state control and condenser
coil temperature sensor for controlling condenser-fan
motor operation, which shall allow unit to operate
down to 0° F outdoor ambient temperature.

9. Filter Rack Kit:

Shall provide filter mounting for downflow applications.

10. Controls Upgrade Kit:

Shall

provide

high

and

low

pressure

safety

protection.

11. Square-To-Round Duct Transitions:

Shall have the ability to convert the supply and return
openings from rectangular to round.

12. Compressor Protection:

Solid-state control shall protect compressor by pre-
venting ‘‘short cycling.’’

13. Duct Conversion Kit:

Shall enable conversion of a factory supplied side
discharge unit to downflow discharge airflow unit.

14. Crankcase Heater:

Shall provide anti-floodback protection for low-load
cooling applications.

15. High Altitude Kit:

Shall consist of natural gas orifices to compensate
for gas heat operation at 2001 to 6000 ft above sea
level.

16. Low NO

x

Kit:

Shall provide NO

x

reduction to values below

40 nanograms/joule to meet California emission
requirements.

17. Compressor Hard Start Kit:

Shall provide additional starting torque for single-
phase compressors.