APPLICATION DATA

1. Condensate trap — A 2-in. condensate trap must be field

supplied.

2. Ductwork — Secure downflow discharge ductwork to roof

curb. For horizontal discharge applications, attach ductwork
to unit with flanges.

3. To convert a unit to downflow discharge — Units are

equipped with factory-installed inserts in the downflow
openings. Remove the inserts similar to removing an electri-
cal knock-out. Use an accessory duct cover to seal the hori-
zontal discharge openings in the unit. Units installed in
horizontal discharge orientation do not require duct covers.

4. Airflow — Units are draw-thru in the Cooling mode and

blow-thru in the Heating mode.

5. Maximum cooling airflow — To minimize the possibility of

condensate blow-off from the evaporator, airflow through the
units should not exceed 450 cfm/ton.

6. Minimum cooling airflow — The minimum cooling airflow is

350 cfm/ton.

7. Minimum ambient operating temperature — All standard

units have a minimum ambient operating temperature of
40 F. With accessory low ambient temperature kit, units can
operate at temperatures down to 0° F.