SECTION 3 - TROUBLESHOOTING

3-8

– JLG Lift –

3121111

Table 3-4. Electrical System Troubleshooting

TROUBLE

PROBABLE CAUSE

REMEDY

HAND CONTROLLER

Regardless of which way handle is moved, only
one function occurs

Improper or loose wiring to the solenoid(s)

Check all wiring for proper connections

Directional valve stuck in one direction

Repair or replace valve

Valve will not function when handle is moved in
either direction

Joystick not activated within the 3 seconds after
function switch was depressed

Reactivate function switch

No electrical power to handle

Check electrical input to hand controller (12V)

No electrical power to valve

Check electrical output of printed circuit board and
electrical signal at the valve

Improper ground

Check for proper grounding of handle

Defective controller

Repair or replace controller

Microswitches on controller bad or need adjust-
ment

Adjust or replace switches

CONTROL SWITCHES

No response to a function control switch

Emergency stop switch not positioned properly

Place emergency stop switch to on

Platform/Ground select switch not positioned
properly

Place switch to platform or ground, as necessary

Circuit breaker open

Determine and correct cause. Reset circuit
breaker

No voltage present at emergency stop switch

Check battery cable from battery to emergency
stop switch for proper connection or damage.
Repair or replace cable as necessary

Emergency stop switch not functioning properly

Replace switch

No voltage supplied to start relay from emergency
stop switch

Check battery cable from switch to relay for proper
connection or damage. Repair or replace cable as
necessary

No voltage input at terminal strip

Check wire from battery to terminal strip for proper
connection or damage. Repair or replace cable as
necessary

No voltage present at circuit breaker

Check wire from terminal strip to battery for proper
connection or damage. Repair or replace cable as
necessary

Defective circuit breaker

Replace circuit breaker

No voltage present at Platform/Ground select
switch

Unplug ground control box harness from platform
receptacle. check wire from applicable pin in plug
to control box power switch for proper connection.
Using suitable test meter, perform continuity test
on wire. Repair or replace harness as necessary

Defective Platform/Ground select switch

Replace Platform/Ground select switch