SECTION 2 - SERVICE PROCEDURES

3120728

– JLG Lift –

2-15

2.6

PLATFORM CONTROL BOX SERVICE
PROCEDURES

Joystick Calibration Procedure

1.

Turn off all power to the platform control.

2.

Move the joystick to the maximum forward position
and hold it there.

NOTE: Joystick will be held in the maximum forward position

until asked to release it in Step 5.

3.

Turn on power to the platform control, nine (9) LED’s
will flash rapidly on the platform control touch pad.

4.

Depress the horn switch pad, the alarm will sound
for about one (1) second, then release the horn pad.

5.

Now release the joystick to the neutral position.

6.

Turn off system power.

The joystick calibration is now complete.

Figure 2-14. Platform Control Box Assembly (Exploded View)

JOYSTICK

ASSEMBLY

PRIOR TO

S/N- 02996

(USED THE

TOUCH PAD

ENABLE

SWITCH)

JOYSTICK ASSEMBLY

S/N- 02996 TO PRESENT

(INCLUDES DRIVE ENABLE BUTTON)