Storage, Daily and periodic inspection – Tsurumi PU Submersible Vortex Sewage Pump User Manual

Page 17

Advertising
background image

-16-

Storage

If the pump will not be operated for a long period of time, pull the pump up, wash the

pump, allow it to dry, and store it indoors.

Note:

For reinstallation, be sure to perform a trial operation before putting the pump into opera-

tion.

If the pump remains immersed in water, operate it on a regular basis (i.e. once a week).

Note:

Refer to section "Oil Inspection and Change Procedures" below for further detail.

Interval

Monthly

Daily

Inspection Item

Yearly

Semi-yearly

Measuring the operating current

Measuring the insulation resistance

Note: The motor must be inspected if the insulation resistance is considerably lower

than the last inspection.

Inspecting oil (models with 0.15~0.75kW power output)

3,000 hours or 12 months, whichever comes first

Inspecting oil (models with 1.5kW power output)

6,000 hours or 12 months, whichever comes first

Power supply voltage variation

= within ±10% of the rated voltage

Measuring the power voltage

Once every

2 years

Once every

2 to 5 years

Changing oil (models with 0.15~0.75kW power output)

Note: The inspection and replacement of the mechanical seal requires specialized

equipment. To have this operation performed, contact the dealer where this

equipment was purchased, or the Tsurumi sales office in your area.

Overhaul

Note: To overhaul the pump, contact the dealer where it was purchased, or the

Tsurumi sales office in your area.

4,500 hours or 24 months, whichever comes first

Changing oil (models with 1.5kW power output)

9,000 hours or 24 months, whichever comes first

Changing the mechanical seal (models with 0.15~1.5kW power output)

Insulation resistance reference value = 1MΩ minimum

Inspecting the pump A noticeable drop in performance

may indicate wear on the impeller or

other parts, or else clogging of the

strainer. Replace any worn parts, or

remove the clogged debris.

Inspecting the

operation of air

release valve

Check to confirm that the air release

valve (air-lock prevention device)

works normally when you start the

pump.

Inspection of lifting

Replace if damage, corrosion, or wear has occurred to the chain or

rope. Remove if foreign object is attaching to it.

To be within the rated current

The pump must be overhauled even if the pump appears normal during operation.

Especially, the pump may need to be overhauled earlier if it is used continuously.

air

release

valve

Section of a pump casing

Inspection of the operation

of air release valve

Daily and Periodic Inspection