Caution, Installing the float, Attaching a chain to suspend the pump – Tsurumi PU Submersible Vortex Sewage Pump User Manual

Page 9

Advertising
background image

-8-

Installing the Float

Insert the float pipe into the holder, and use

a Phillips screwdriver to tighten the set screw.

Although the float level is preset, follow the

procedures given below to change the level.
(1) Loosen the screw and adjust the height at

the top and the bottom of the float pipe to

set the starting and stopping water levels.

(2) After completing the setting, tighten the

screws to secure both the top and the bot-

tom of the float pipe.

When you are going to set a lower start level,

pay attention not to operate the pump at

the levels below the C.W.L. longer than 15

minutes.
* In the case of an automatic alternating

model, apply the same procedures to set

the parallel operating water level. Then,

remove the alternating start float by loos-

ening its screw, set the alternating starting

water level as desired, and secure the alter-

nating start float in place by tightening the

screw.

* To prevent unintended operation, face the

floats outward.

To change the operating water level on

an automatic alternating model, perform

the setting by referring to the diagram

on the right. There is no need to change

its stopping water level.
* After changing the water level on an

automatic alternating model, make

sure to adjust its automatic side.

* Pay attention to the positional rela-

tionship between floats 3, 4, and 5 to

perform the settings.

Number

Name

Color

1

No. 1 Pump Stop Float

Red

2

No. 2 Pump Stop Float

Red

3

No. 2 Pump Alternating Start Float Yellow

4

No. 1 Pump Start Float

Yellow

5

Green

No. 1 Pump / No. 2 Pump

Parallel Operation Float

Holder

Start Float

Stop Float

Float Pipe

Water Level Adjustment

Set Screw

Start Float

Stop Float

Set Screw

Adjusting the start float to set

the starting water level as

desired:

Setting the stop float water

level high:

Start Float

Stop Float

Set Screw

Water Level

Adjustment

L

L

Setting the start float

water level low:

Make sure that the

float lead wire length

L is 40mm.

Failure to observe

this precaution could

cause the pump to

operate improperly.

Make sure that the

float lead wire length

L is 200mm.

Failure to observe

this precaution could

cause the pump to

operate improperly.

Automatic Pump

(No. 1 Pump)

Automatic Alternating Pump

(No. 2 Pump)

Starting

Water Level

Starting

Water

Level

Stopping

Water

Level

Stopping

Water

Level

Parallel

Operation

Water Level

50mm

minimum

50mm

minimum

1

3

4

5

2

Attaching a Chain to Suspend the Pump

Chain

Bolt

Shackle

Washer (for 1.5kW)

Refer to the illustration on the right in order to suspend

the pump by a chain. (On a model with a 1.5kW power

output, use a washer.)

CAUTION

Make sure that the chain does not

become twisted during installation.

Failure to observe this precaution

could cause the chain to break and the

pump to fall and break, which could

lead to injury.

Note:

To use the pump with the guide rail, refer to the

separate operation manual entitled "Guide Rail".