User Manual Version 1.0

MB5001C series 1-port Modbus Gateway

Copyright © 2010 Atop Technologies, Inc.

All rights reserved. Designed in Taiwan.

9

3. Software Setup

MB5001C Modbus Gateway is shipped with default settings shown in the following table:

Property

Default Value

IP Address

10.0.50.100

Gateway

10.0.0.254

Subnet Mask

255.255.0.0

User Name

admin

Password

Null(leave it blank)

COM 1

9600,None, 8, 1, No flow control, buffer disabled, packet delimiter timer 2ms

Link 1

Type: TCP Server, Listen port 4660, Filter=0.0.0.0

SysName of SNMP

name

SysLocation of SNMP location

SysContact of SNMP

contact

3.1 Configuration by DeviceView

3.1.1 Static IP

Use DeviceView that comes with product CD to configure the network parameters of MB5001C.
Please click “Configuration” button(ref Figure 3.1) then give it a static IP information.( Figure 3.2)

Figure 3.1 Configure by DeviceView