10

2.3

95-8613

sTATus InFo menu
This menu (read only) shows extensive status information about the detector.

1) warm up (Y/n)

Device is in the power-up time delay (warm-up) mode.

2) Fire (Y/n)

Indicates “Y” if the device is in a fire alarm status — analog output is at

20

mA,

fire alarm relay is actuated and LED is red.

3) Automatic

oi Fault (Y/n) Automatic

oi Fault. Check viewing windows and oi reflector plate for cleanliness.

4) diminish. detect. Flt (Y/n)

Diminished Detection Fault. Excessive background IR radiation. Eliminate IR

interference and/or re-aim/orient detector.

5) detect. disable Flt (Y/n)

Flame detector function has been disabled. Check viewing windows for

cleanliness and/or presence of excessive background IR signal.

6) sensor hdwr Fault (Y/n)

Sensor hardware fault.

7) hIB hardware Fault (Y/n)

HART Interface Board hardware fault.

8) Internal Com. Flt

Internal communication fault.

9) Incompatible Fault

Sensor module firmware version is not compatible with HART Interface Board.

10) voltage Fault (Y/n)

Detector operating voltage is out of tolerance.

11) hardware menu

Refer to sub-menu.

12)

oi menu

Refer to sub-menu.

Device Info Menu

1) General Info Menu

2) HART Info Menu

3) Status Info Menu

4) Detector Settings

5) History Menu

X3302 Root Menu

1) Fire (Yes/No)

2) Fault (Yes/No)

3) Device Info Menu

4) Command Menu

5) Device Setup Menu

Status Info Menu

1) Warm Up (Y/N)

2) Fire (Y/N)

3) Automatic Oi Fault (Y/N)

4) Diminish. Detect. Flt (Y/N)

5) Detect. Disable Flt (Y/N)

6) Sensor Hdwr. Fault (Y/N)

7) HIB Hardware Fault (Y/N)

8) Internal Com. Flt (Y/N)

9) Incompatible Fault (Y/N)

10) Voltage Fault (Y/N)

11) Hardware Menu

12) Oi Menu