Det-Tronics X3302 Multispectrum IR Flame Detector with HART User Manual

Page 15

Advertising
background image

13

2.3

95-8613

deTeCTor seTTIngs
This menu shows factory settings relating to relay operation, detector sensitivity and response.

1) Fire relay L/nL

Fire relay contacts, latching (L) or non-latching (NL).

2) Fire relay ne/nde

Fire relay coil, normally energized (NE) or normally de-energized (NDE).

3) Fault relay L/nL

Fault relay contacts, latching (L) or non-latching (NL).

4) Fault relay ne/nde

Fault relay coil, normally energized (NE) or normally de-energized (NDE).

5) Aux relay L/nL

Auxiliary relay contacts, latching (L) or non-latching (NL).

6) Aux relay ne/nde

Auxiliary relay coil, normally energized (NE) or normally de-energized (NDE).

7) sensitivity

Detector sensitivity setting: Very high, High, Medium, or Low.

8) response Time

Fire alarm processing time in seconds.

hIsTorY menu
This menu provides historical information about the detector. Up to

32

events in each of the three categories will

be kept in non-volatile memory. When the log is full, the oldest event will be overwritten. The most recent event

will be displayed first.

1) Alarm Log

Scroll through

32

Alarm Logs with time, date and temperature stamp.

2) Fault Log

Scroll through

32

Fault Logs with time, date and temperature stamp.

3) general Log

Scroll through

32

General Logs with time, date and temperature stamp.

History Menu

1) Alarm Log
2) Fault Log
3) General Log

Device Info Menu

1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu

X3302 Root Menu

1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu

Device Info Menu

1) General Info Menu

2) HART Info Menu

3) Status Info Menu

4) Detector Settings

5) History Menu

X3302 Root Menu

1) Fire (Yes/No)

2) Fault (Yes/No)

3) Device Info Menu

4) Command Menu

5) Device Setup Menu

Detector Settings

1) Fire Relay L/NL

2) Fire Relay NE/NDE

3) Fault Relay L/NL

4) Fault Relay NE/NDE

5) Aux Relay L/NL

6) Aux Relay NE/NDE

7) Sensitivity

8) Response Time

Advertising