hArdwAre menu

1) heater Power

Actual heater power (

0

to

100%

). Heater prevents condensation and icing on the

detector optics.

2) heater setpoint

Maximum amount of heater power allowed (in percent of full power).

3) Temperature

Actual internal temperature of detector.

4) Temp setpoint

Internal target temperature that the heater will attempt to maintain (in degrees C).

5) Temp range Fault

Detector integral temperature out of range — Operating range: –

40°

F to +

167°

F

(–

40°

C to +

75°

C).

6) voltage

Actual detector supply voltage (must be

18

to

30

Vdc).

7) voltage Fault (Y/n)

Supply voltage is out of range. Operating voltage must be

18

to

30

Vdc.

Hardware Menu

1) Heater Power

2) Heater Setpoint

3) Temperature

4) Temp Setpoint

5) Temp Range Fault

6) Voltage

7) Voltage Fault (Y/N)

Device Info Menu

1) General Info Menu

2) HART Info Menu

3) Status Info Menu

4) Detector Settings

5) History Menu

X3302 Root Menu

1) Fire (Yes/No)

2) Fault (Yes/No)

3) Device Info Menu

4) Command Menu

5) Device Setup Menu

Status Info Menu

1) Warm Up (Y/N)

2) Fire (Y/N)

3) Automatic Oi Fault (Y/N)

4) Diminish. Detect. Flt (Y/N)

5) Detect. Disable Flt (Y/N)

6) Sensor Hdwr Fault (Y/N)

7) HIB Hardware Fault (Y/N)

8) Internal Com. Flt (Y/N)

9) Incompatible Fault (Y/N)

10) Voltage Fault (Y/N)

11) Hardware Menu

12) Oi Menu