Det-Tronics X3302 Multispectrum IR Flame Detector with HART User Manual

Page 4

Advertising
background image

2

2.3

95-8613

24 VDC

mA

PLC

+

600 MAX*

AT

24 VDC

+

B

2393

9

8

7

6

5

4

3

2
1

19

18

17

16

15

14

13

12

11

mA +

mA + REF

mA –

24 VDC +

24 VDC –

29

28

27

26

25

24

23

22

21

X

3302 IR DETECTOR

Figure

1

—X

3302

Detector Wired for Non-Isolated

0

to

20

mA

Current Output (Sourcing)

24 VDC

mA

PLC

+

600 MAX*

AT

24 VDC

+

B

2394

9

8

7

6

5

4

3

2
1

19

18

17

16

15

14

13

12

11

mA +

mA –

mA – REF

24 VDC +

24 VDC –

29

28

27

26

25

24

23

22

21

X

3302 IR DETECTOR

Figure

3

—X

3302

Detector Wired for Non-Isolated

0

to

20

mA

Current Output (Sinking)

24 VDC

mA

PLC

+

600 MAX*

AT

24 VDC

+

B

2395

9

8

7

6

5

4

3

2
1

19

18

17

16

15

14

13

12

11

mA +

mA –

24 VDC +

24 VDC –

29

28

27

26

25

24

23

22

21

X

3302 IR DETECTOR

+

24 VDC

Figure

2

—X

3302

Detector Wired for Isolated

0

to

20

mA

Current Output (Sourcing)

24 VDC

mA

PLC

+

600 MAX*

AT

24 VDC

+

B2396

9

8

7

6

5

4

3

2
1

19

18

17

16

15

14

13

12

11

mA +

mA –

24 VDC +

24 VDC –

29

28

27

26

25

24

23

22

21

X

3302 IR DETECTOR

+

24 VDC

Figure

4

—X

3302

Detector Wired for Isolated

0

to

20

mA

Current Output (Sinking)

250

9

8

7

6

5

4

3

2

1

19

18

17

16

15

14

13

12

11

mA +

mA –

mA – REF

24 VDC +

24 VDC –

29

28

27

26

25

24

23

22

21

X

3302 IR DETECTOR

24 VDC

+

B

2392

Figure

5

—Wiring the X

3302

for Benchtop Testing/Programming

Using HART Protocol

*Nominal input impedance of PLC =

250 ohms.

Maximum loop impedance including input impedance of PLC =

600 ohms.