Det-Tronics X2200 UV Flame Detector User Manual
Page 13
![background image](/manuals/557677/13/background.png)
11
95-8549
13.1
EQp Model
1. Connect external wires to the appropriate terminals
inside the device junction box, shown in Figure 13.
See Figure 14 for terminal identification.
2. Connect the shield of the power cable to “earth
ground” at the power source.
3. Connect shields for the LON cable as indicated. See
Figure 15.
NOTE
DO NOT ground any shields at the detector housing.
4. With input power disconnnected, set the device
network address. (See “Setting Device Network
Addresses” section of this manual for switch
setting procedure.)
5. Check all field wiring to be sure that the proper
connections have been made.
6. Replace the device cover and apply input power.
7. Make the final sighting adjustments and use a 14 mm
hex wrench to ensure that the mounting arm assembly
is tight.
NOTE
Refer to the Eagle Quantum Premier system
manual (95-8533) for information regarding power
requirements, network communication cable
requirements, and configuration.
6
5
4
3
2
1
16
15
14
13
12
11
COM SHIELD
COM SHIELD
COM 1 A
COM 2 A
COM 1 B
COM 2 B
POWER SHIELD
POWER SHIELD
24 VDC +
24 VDC +
24 VDC –
24 VDC –
B2089
figure 13—X2200 terminal block (eQp model)
figure 14—Wiring terminal identification for X2200 eQp model