Det-Tronics X2200 UV Flame Detector User Manual

Page 13

Advertising
background image

11

95-8549

13.1

EQp Model
1. Connect external wires to the appropriate terminals

inside the device junction box, shown in Figure 13.

See Figure 14 for terminal identification.

2. Connect the shield of the power cable to “earth

ground” at the power source.

3. Connect shields for the LON cable as indicated. See

Figure 15.

NOTE

DO NOT ground any shields at the detector housing.

4. With input power disconnnected, set the device

network address. (See “Setting Device Network

Addresses” section of this manual for switch

setting procedure.)

5. Check all field wiring to be sure that the proper

connections have been made.

6. Replace the device cover and apply input power.
7. Make the final sighting adjustments and use a 14 mm

hex wrench to ensure that the mounting arm assembly

is tight.

NOTE

Refer to the Eagle Quantum Premier system
manual (95-8533) for information regarding power
requirements, network communication cable
requirements, and configuration.

6

5

4

3

2

1

16

15

14

13

12

11

COM SHIELD

COM SHIELD

COM 1 A

COM 2 A

COM 1 B

COM 2 B

POWER SHIELD

POWER SHIELD

24 VDC +

24 VDC +

24 VDC –

24 VDC –

B2089

figure 13—X2200 terminal block (eQp model)

figure 14—Wiring terminal identification for X2200 eQp model