95-8549

14

13.1

startup proceDure

When installation of the equipment is complete, perform

the “Fire Alarm Test” below.

FIRE ALARM TEsT
1. Disable any extinguishing equipment that is

connected to the system.

2. Apply input power to the system.
3. Initiate an

oi

test. (See “Magnetic

oi

/ Manual

oi

under Optical Integrity in the Description section of

this manual.

4. Repeat this test for all detectors in the system. If

a unit fails the test, refer to the “Troubleshooting”

section.

5. Verify that all detectors in the system are properly

aimed at the area to be protected. (The Q1201C

Laser Aimer is recommended for this purpose.)

6. Enable extinguishing equipment when the test is

complete.

troubleshooting

WarnIng

The sensor module (“front” half of the detector)
contains no user serviceable components
and should never be opened. The terminal
compartment is the only part of the enclosure that
should be opened by the user in the field.

1. Disable any extinguishing equipment that is

connected to the unit.

2. Inspect the viewing windows for contamination and

clean as necessary. (Refer to the “Maintenance”

section for complete information regarding cleaning

of the detector viewing windows.)

3. Check input power to the unit.
4. If the fire system has a logging function, check

the fire panel log for output status information.

See Table 4 for information regarding 0 to 20 mA

output.

5. Turn off the input power to the detector and check all

wiring for continuity. Important: Disconnect wiring

at the detector before checking system wiring for
continuity.

6. If all wiring checks out and cleaning of the

oi

plate/

window did not correct the fault condition, check for

high levels of background UV radiation by covering

the detector with the factory supplied cover or

aluminum foil. If the fault condition clears, extreme

background UV radiation is present. Re-adjust the

view of the detector away from the UV source or

relocate the detector.

If none of these actions corrects the problem, return the

detector to the factory for repair.

NOTE

It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.

maintenance

Important

Periodic flamepath inspections are not
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of the
flamepaths.

WarnIng

The sensor module (“front” half of the detector)
contains no user serviceable components
and should never be opened. The terminal
compartment is the only part of the enclosure that
should be opened by the user in the field.

NOTE

Refer to the X2200 Safety manual (95-8672) for
specific requirements and recommendations
applicable to the proper installation, operation,
and maintenance of all SIL-Certified X2200 Flame
Detectors.

To maintain maximum sensitivity and false alarm

resistance, the viewing windows of the X2200 must be

kept relatively clean. Refer to the following procedure for

cleaning instructions.

1If fault continues, return device to factory for repair.

2See “Maintenance” section for cleaning procedure.

table 4—current Level output troubleshooting guide

Current Level

(±0.3 mA)

status

Action

0 mA

Power Fault

Check system wiring.

1 mA

General Fault

Cycle power.1

2 mA

oi

Fault

Clean windows.2

4 mA

Normal Operation

16 mA

Hi Background UV

Fault

Remove UV source

or aim detector away

from UV source.

20 mA

Fire Alarm