Det-Tronics X2200 UV Flame Detector User Manual

Page 24

Advertising
background image

22

95-8549

13.1

FM Approval and performance Report – Continued

FIELD OF VIEW

Very high sensitivity

Fuel

size

Distance

feet (m)

horizontal

(degrees)

Typical

Response Time

(seconds)*

Vertical

(degrees)

Typical

Response

(seconds)*

Mode

n-Heptane

1 x 1 foot

42.5

(13)

+45

–45

2
2

+45

–30

2
2

Low Arc

Methane

32 inch plume

50

(15.2)

+45

–45

2
2

+45

–30

2
2

Low Arc

*Add 2 seconds for EQP model.

high sensitivity

Fuel

size

Distance

feet (m)

horizontal

(degrees)

Typical

Response Time

(seconds)*

Vertical

(degrees)

Typical

Response

(seconds)*

Mode

n-Heptane

1 x 1 foot

30

(9.1)

+45

–45

1
1

+45

–30

1
1

Standard

n-Heptane

1 x 1 foot

30

(9.1)

+45

–45

1
1

+45

–30

1
1

Hi Arc

n-Heptane

1 x 1 foot

30

(9.1)

+45

–45

2
2

+45

–30

2
2

Very Hi Arc

Methane

32 inch plume

40

(12.2)

+45

–45

1
1

+45

–30

1
1

Standard

Methane

32 inch plume

40

(12.2)

+45

–45

1
1

+45

–30

1
1

Hi Arc

Methane

32 inch plume

35

(10.7)

+45

–45

1
1

+45

–30

1
1

Very Hi Arc

*Add 2 seconds for EQP model.

Medium sensitivity

Fuel

size

Distance

feet (m)

horizontal

(degrees)

Typical

Response Time

(seconds)*

Vertical

(degrees)

Typical

Response

(seconds)*

Mode

n-Heptane

1 x 1 foot

17.5

(5.3)

+45

–45

1
1

+45

–30

1
1

Standard

n-Heptane

1 x 1 foot

25

(7.6)

+45

–45

1
1

+45

–30

1
1

Hi Arc

Methane

32 inch plume

30

(9.1)

+45

–45

2
2

+45

–30

2
2

Standard

Methane

32 inch plume

30

(9.1)

+45

–45

1
1

+45

–30

1
1

Hi Arc

*Add 2 seconds for EQP model.

Advertising