Appendix d, Iecex approval – Det-Tronics X2200 UV Flame Detector User Manual

Page 29

Advertising
background image

27

95-8549

13.1

appenDiX D

IECEx AppROVAL

IECEx CERTIFICATE OF CONFORMITy

DEMkO
IECEx ULD 06.0018X
Ex d e IIC T6-T5 Gb

Ex d IIC T6-T5 Gb

Ex tb IIIC T80°C

Ex tb IIIC T80°C

T6 (Tamb = –50°C to +60°C)

or

T6 (Tamb = –55°C to +60°C)

T5 (Tamb = –50°C to +75°C)

T5 (Tamb = –55°C to +75°C)

IP66/IP67.

IP66/IP67.

Compliance with:
IEC 60079-0: 2007, Ed. 5

IEC 60079-1: 2007, Ed. 6

IEC 60079-7: 2006, Ed. 4

IEC 60079-31: 2008, Ed. 1

EN / IEC 60529: 2001.

INsTALLATION INsTRuCTIONs
The field wiring connections in the terminal compartment are suitable certified and accepts wiring specifications from

14-24 AWG or 2.5-0.2 mm

2

.

The flame detector model X2200UV shall be installed according to the instructions given by the manufacturer.

The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the

terminal compartment in type of explosion protection flameproof enclosure "d", or in type of explosion protection

increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e". They

shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.

Unused entries shall be closed with suitable certified blanking elements.

The metal housing for the Ultraviolet (UV) flame detector type X2200 must be electrically connected to earth ground.

For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum

ambient temperature.

special conditions for safe use:
The EOL resistor can only be used within the flameproof terminal compartment.

EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed

2.5 watts.

The Ultraviolet (UV) flame detector type X2200 is to be installed in places where there is a low risk of mechanical

damage.

The following accessories are IECEx approved for use with the X2200 Flame Detector:

part Number

Description

007290-001

Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors

007290-002

Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only

011385-001

Q9033 Collar Attachment

Advertising