CLEANINg pROCEDuRE

CaUtIon

Disable any extinguishing equipment that is
connected to the unit to prevent unwanted
actuation.

To clean the windows and

oi

plate, use the window

cleaner (p/n 001680-001) with a soft cloth, cotton swab,

or tissue and refer to the following procedure:

1. Disable any extinguishing equipment that is

connected to the unit.

NOTE

Remove input power when cleaning the detector
windows. The rubbing motion on the surface of
the windows during cleaning can create static
electricity that could result in unwanted output
activation.

2. Clean the viewing window and reflective surfaces

of the

oi

plate using a clean cloth, cotton swab,

or tissue with the window cleaning solution. Use

Isopropyl alcohol for contaminations that the Det-

Tronics window cleaning solution can not remove.

If a fault condition is still indicated after cleaning,
remove and clean the

oi

plate using the

oi

Plate

Removal and Replacement procedure.

Important

When used in extreme environments, the reflective
surface of the detector

oi

plate may eventually

deteriorate, resulting in reoccurring

oi

faults and

the need for

oi

plate replacement.

oi

pLATE REMOVAL AND REpLACEMENT

1. Disable any extinguishing equipment that is

connected to the unit.

2. Loosen the two captive screws, then grasp the

oi

plate by the visor and remove it from the detector.

See Figure 18.

3. Install the new (or cleaned)

oi

plate.

4. Recalibrate the detector's

oi

system. Refer to the

Inspector Monitor manual (95-8581) for instructions
regarding

oi

plate replacement and

oi

system

recalibration.

CaUtIon

Do not replace the

oi

reflector plate without also

recalibrating the

oi

system.

Recalibration of the

oi

system requires the use of the

Inspector Connector Cable and Inspector Monitor
Software. These two items are included in the

oi

replacement kit, or they can be purchased separately.

See Ordering Information for details.

pERIODIC ChECkOuT pROCEDuRE
In compliance with SIL 2, a checkout of the system using
the Mag

oi

or Man

oi

feature should performed regularly

to ensure that the system is operating properly. Refer

to Table 1 in the X2200 Safety manual (95-8672) for

frequency of proof tests. To test the system, perform the

“Fire Alarm Test” as described in the “Startup Procedure”

section of this manual.

CLOCk bATTERy
The real time clock has a backup battery that will

operate the clock with no external power. Return the

device to the factory for battery replacement if needed.

NOTE

If the backup battery is depleted, there is no effect
on the operation of the flame detector, but the time
stamping of the data log may be affected.

LOOSEN TWO CAPTIVE SCREWS

GRASP VISOR AND
REMOVE

oi PLATE

B2211