installation

NOTE

The recommended lubricant for threads and
O-rings is a silicone free grease (p/n 005003-
001) available from Det-Tronics. Under no
circumstances should a lubricant containing
silicone be used.

DETECTOR pOsITIONINg
Detectors should be positioned to provide the best

unobstructed view of the area to be protected.

The following factors should also be taken into

consideration:
• Identify all high risk fire ignition sources.
• Be sure that enough detectors are used to adequately

cover the hazardous area.

• Be sure that the unit is easily accessible for cleaning

and other periodic servicing.

• Verify that all detectors in the system are properly

located and positioned so that any fire hazards are

within both the Field of View (FOV) and detection

range of the detector. The Q1201C Laser Aimer

is recommended for establishing the detector's

FOV. Refer to Appendix A for specific information

regarding detector range and FOV.

• The detector should be aimed downward at least 10

to 20 degrees to allow lens openings to drain (see

Figure 1). The detector should be positioned so

that its FOV does not cover areas outside the
hazardous area.

This will minimize the possibility

of false alarms caused by activities outside the area

requiring protection.

• The detector must be mounted on a rigid surface in

a low vibration area.

• Dense fog, rain as well as certain gases and vapors

(see Table 3) can absorb UV radiation and reduce

the sensitivity of the detector.

• If possible, fire tests can be conducted to verify

correct detector positioning and coverage.

• For ATEX installations, the X2200 Flame Detector

housing must be electrically connected to earth

ground.

DETECTOR ORIENTATION
Refer to Figure  2 and ensure that the

oi

plate will be

oriented as shown when the X2200 is mounted and
sighted. This will ensure proper operation of the

oi

system and will also minimize the accumulation of
moisture and contaminants between the

oi

plate and

the viewing windows.

Important

If removed, the

oi

plate must be securely

tightened to ensure proper operation of the

oi

system (40 oz./inches [28.2 N .cm] recommended).

CENTER AXIS
OF DETECTOR
FIELD OF VIEW

CENTER AXIS
OF DETECTOR
FIELD OF VIEW

INCORRECT

CORRECT

NOTE: DETECTOR MUST ALWAYS BE AIMED

DOWNWARD AT LEAST 10 TO 20 DEGREES.

D1974

figure 1—Detector orientation relative to horizon

figure 2—front view of the X2200

UV VIEWING WINDOW

oi PLATE

PLACE MAGNET

HERE TO INITIATE

MAGNETIC

oi

oi MAGNET

DETECTOR

STATUS INDICATOR

B2171