Optical integrity ( oi), Startup procedure – Det-Tronics X3300EXE Protect-IR Multispectrum IR Flame Detector User Manual

Page 10

Advertising
background image

OPTICAL INTEGRITY (

oi)

AUTOMATIC

oi

The X3300 includes the Automatic Optical Integrity (

oi)

feature — a calibrated performance test that is
automatically performed once per minute to verify
complete detector operation capabilities. No testing
with an external test lamp is required. The detector
automatically performs the same test that a
maintenance person with a test lamp would perform —
once every minute, 60 times per hour. A successful
automatic

oi test

does not

produce an alarm condition.

The Protect•ir signals a fault condition when less than
50% of the detection range remains. This is indicated
by the Fault relay and is evident by the amber color of
the LED on the face of the detector. See the
“Troubleshooting” section for further information.

MANUAL

oi

The detector also incorporates a manual

oi feature that

provides the same test as the automatic

oi, and in

addition actuates the Alarm relay to verify output
operation. The manual

oi feature is available in all

models and can be performed at any time.

This test

requires bypass of all extinguishing devices to avoid
release resulting from a successful test.

The manual

oi test is activated by connecting the white

lead to power supply minus. This places the detector in
a special operating mode. First, the device de-latches
any latching outputs. Next, the IR emitters are activated.
If the resulting signals meet the test criteria, the Alarm
relay changes state and the indicating LED changes to
red. This condition remains until the white lead is
disconnected from dc minus. If the test criteria are not
met, no alarm is produced and no fault is generated.
See the “Troubleshooting” section for further details.

STARTUP PROCEDURE

When installation of the equipment is complete, perform
the “Fire Alarm Test” below.

Allow 20 to 30 minutes for the detector optics to reach
equilibrium. Housing will be warm to the touch.

8

24 VDC

4 TO 20 MA

PLC

+

875

MAX

AT 24 VDC

4 TO 20

MA

Oi

–24 VDC

+24 VDC

1

2

3

4

5

+

+

A2005

Oi TEST1

2

Figure 7A—X3300 Detector Wired for Non-Isolated 4 to 20 ma

Current Output (Sourcing)

24 VDC

4 TO 20 MA

PLC

+

875

MAX

AT 24 VDC

4 TO 20

MA

Oi

–24 VDC

+24 VDC

1

2

3

4

5

+

+

A2006

Oi TEST1

2

Figure 7B—X3300 Detector Wired for Non-Isolated 4 to 20 ma

Current Output (Sinking)

24 VDC

4 TO 20 MA

PLC

+

24 VDC

+

875

MAX

AT 24 VDC

4 TO 20

MA

Oi

–24 VDC

+24 VDC

1

2

3

4

5

+

+

A2007

Oi TEST1

2

Figure 7C—X3300 Detector Wired for Isolated 4 to 20 ma

Current Output (Sourcing)

24 VDC

4 TO 20 MA

PLC

+

24 VDC

+

875

MAX

AT 24 VDC

4 TO 20

MA

Oi

–24 VDC

+24 VDC

1

2

3

4

5

+

+

2008A

Oi TEST1

2

Figure 7D—X3300 Detector Wired for Isolated 4 to 20 ma

Current Output (Sinking)

NOTES:

1.INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE

INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE
PANEL. TEST SWITCHES ARE NOT SUPPLIED.

2.SHIELD IS CONNECTED TO EARTH GROUND THROUGH

A 0.47µF/400V FILM CAPACITOR.