Appendix a response characteristics of the x3300 – Det-Tronics X3300EXE Protect-IR Multispectrum IR Flame Detector User Manual

Page 17

Advertising
background image

15

95-8502

APPENDIX A

Response Characteristics of the X3300

RESPONSE CHARACTERISTICS:

Fuel

Size

Distance

Average Response Time

(feet)

(seconds)

Gasoline

1 x 1 foot

100

6.0

Gasoline

1 x 1 foot

50

3.8

Diesel**

1 x 1 foot

70

7.4

Methanol

1 x 1 foot

70

9.7

Methane

30 inch plume

65

2.4

Methane

30 inch plume

55

0.8

JP-5**

2 x 2 foot

100

5.7

** 10 second pre-burn from ignition.

Medium Sensitivity

Fuel

Size

Distance Average Response Time

(feet)

(seconds)

Gasoline

1 x 1 foot

210*

8.4

Gasoline

1 x 1 foot

100

1.4

Diesel**

1 x 1 foot

150*

9.6

Methanol

1 x 1 foot

150*

5.7

Methane

30 inch plume

100

2.5

JP-5**

2 x 2 foot

210*

8.5

JP-5**

2 x 2 foot

100

2.6

Office

18” x 16” x 10”

100

4.5

Paper 0.5 lb.

Corrugated

18” x 36”

100

15.8

Panel

* Outdoor test condition.
** 10 second pre-burn from ignition.

Very High Sensitivity

Advertising