Factory configurable options include:

• Automatic or Manual Optical Integrity (

oi)

• Fire and Fault Relay Operation

– Normally Open (N.O.) or Normally Closed (N.C.)

Contacts

– Normally Energized or Normally De-Energized (Fire

relay)

– Latching or Non-latching.

• 4 to 20 mA output.

Table 2—Factory Configuration Options (Not Changeable in the Field)

Option

Available Configurations

Sensitivity

• Detects 1 square foot gasoline fire at 210 feet (very high

sensitivity) or 100 feet (medium sensitivity).

Optical Integrity (

oi)

*

Automatic

oi - Automatically checks internal circuitry and

cleanliness of viewing windows to ensure proper operation.
If a fault condition exists, the amber Fault LED lights.

• Manual

oi - Cleanliness of viewing windows test can be

manually initiated by closing an external switch that is elec-
trically connected between the

oi lead and circuit ground.

Warning:

Successful Manual

oi test results in fire alarm

relay activation and red Alarm LED lights.

• Internal circuitry is automatically tested independent of the

Manual

oi test

Fire Relay

Latching/Non-Latching

• Latching - Relay remains in “Fire” condition after fire has

been detected until X3300 power is cycled.

*

Non-latching - Relay remains in “Fire” condition only as long
as a fire is being detected.

Normally Energized/De-Energized

• Normally Energized - Fire relay is energized in non-alarm

(no fire) condition.

*

Normally De-Energized - Fire relay is de-energized in non-
alarm (no fire) condition.

Contacts Normally Open/Closed

*

Normally Open - Fire relay contacts are open in non-alarm
(no fire) condition.

• Normally Closed - Fire relay contacts are closed in non-

alarm (no fire) condition.

Fault Relay

Latching/Non-Latching

• Latching - Relay remains in “Fault” condition after fault has

been detected until X3300 power is cycled.

*

Non-latching - Relay remains in “Fault” condition only as
long as a fault is being detected.

Normally Energized

*

Normally Energized - Fault relay is energized with no fault
present.

Contacts Normally Open/Closed

*

Normally Open - Fault relay contacts are open when fault is
present.

• Normally Closed - Fault relay contacts are closed when

fault is present.

4 to 20 mA Output

• Current output level indicates detector status condition.

* Standard Configuration

2

Detector Status

LED Indicator

Power On/Normal Operation

Green

(no fault or fire alarm)

Fault Yellow

Fire (Alarm)

Red

Medium Sensitivity

Two Yellow Flashes

During Power-up

Very High Sensitivity

Four Yellow Flashes

During Power-up

Table 1—Detector Status Indicator