Installation, Wiring requirements – Det-Tronics X3300EXE Protect-IR Multispectrum IR Flame Detector User Manual

Page 6

Advertising
background image

INSTALLATION

DETECTOR POSITIONING

Detectors should be positioned to provide the best
unobstructed view of the area to be protected. The
following factors should also be taken into consideration:

• Identify all high risk fire ignition sources.

• Be sure that enough detectors are used to adequately

cover the hazardous area.

• Locate and position the detector so that the fire

hazard(s) are within both the field of view and
detection range of the device. Refer to Appendix A
for specific information.

• Be sure that the unit is easily accessible for cleaning

and other periodic servicing.

• For outdoor applications, the detector should be

aimed downward at least 10 to 20 degrees to allow
lens openings to drain. See Figure 1. The detector
should be positioned so that its field of view does not
cover areas outside the hazardous area. This will
minimize the possibility of false alarms caused by
activities outside the area requiring protection.

• For best performance, the detector should be

mounted on a rigid surface in a low vibration area.

• Dense fog, rain or ice can absorb IR radiation and

reduce the sensitivity of the detector.

• Although IR detectors are less affected by smoke than

other detectors, the X3300 should not be placed
where rising combustion products can obscure its
vision. If smoke is expected before fire, smoke or
other alternative detectors should be used in
conjunction with the X3300. For indoor applications, if
dense smoke is expected to accumulate at the onset
of a fire, mount the detector on a side wall at least a
few feet (approximately 1 meter) down from the
ceiling.

• If possible, fire tests should be conducted to verify

correct detector positioning and coverage.

WIRING REQUIREMENTS

WIRE SIZE AND TYPE

The system should be wired using a 14 to 22 gauge (1.3
to 0.5 mm2) cable. The wire size selected should be
based on the number of detectors connected, the
supply voltage and the cable length. A minimum input
voltage of 18 vdc must be present at the X3300.

The use of shielded cable is recommended to protect
against interference caused by EMI and RFI. When
using cables with shields, terminate the shields as
shown in Figures 6 through 8. Consult the factory if not
using shielded cable.

In applications where the wiring cable is installed in
conduit, the conduit should not be used for wiring to
other electrical equipment.

CAUTION

Installation of the detector and wiring should be
performed only by qualified personnel.

PROTECTION AGAINST MOISTURE DAMAGE

It is important to take proper precautions during
installation to ensure that moisture will not come in
contact with the electrical connections or components
of the system. The integrity of the system regarding
moisture protection must be maintained for proper
operation and is the responsibility of the installer. Units
with M25 threads must use an IP66 washer.

4

Figure 1—Detector Orientation Relative to Horizon

CENTER AXIS
OF DETECTOR
FIELD OF VIEW

CENTER AXIS
OF DETECTOR
FIELD OF VIEW

INCORRECT

CORRECT

NOTE: DETECTOR MUST ALWAYS BE AIMED

DOWNWARD AT LEAST 10 TO 20 DEGREES.

B1974

Advertising