Det-Tronics X3300EXE Protect-IR Multispectrum IR Flame Detector User Manual

Page 19

Advertising
background image

OPTICAL FAULT:

The detector generated an optical fault in the presence of contamination on any single or combination of lens
surfaces verifying that the detector performs an optical integrity (

oi) test for each sensor. Upon removal of the

contaminant the detector fault was cleared and the detector was verified to detect a fire.

RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES:

17

95-8502

False Alarm Source

Distance

Fire Source

Distance

Average Response Time

(feet)

(feet)

(seconds)

Sunlight, direct, modulated, reflected

6-inch propane

6

< 4

Vibration

N/A

6-inch propane

6

< 10

Radio frequency interference

1

6-inch propane

12

< 1

Arc welding

40

1 x 1 foot gasoline

40

3.1

6 kw heater, modulated

100

1 x 1 foot gasoline

100

1.9

6 kw heater, unmodulated

10

1 x 1 foot gasoline

100

5.3

250 w vapor lamp, modulated

3

1 x 1 foot gasoline

100

2.7

300 w incandescent lamp, modulated

3

1 x 1 foot gasoline

100

3.6

500 w unshielded quartz halogen lamp, modulated

8

1 x 1 foot gasoline

100

2.7

1500 w electric radiant heater, modulated

10

1 x 1 foot gasoline

100

4.2

Two 34 w fluorescent lamps, modulated

3

1 x 1 foot gasoline

100

1.7

Very High Sensitivity

False Alarm Source

Distance

Fire Source

Distance

Average Response Time

(feet)

(feet)

(seconds)

Sunlight, direct, modulated, reflected

6-inch propane

6

< 4

Vibration*

N/A

N/A

N/A

N/A

Radio frequency interference

1

6-inch propane

6

< 1

Arc welding

10

1 x 1 foot gasoline

10

0.2

6 kw heater, modulated

100

1 x 1 foot gasoline

100

5.0

6 kw heater, unmodulated

10

1 x 1 foot gasoline

100

10.7

250 w vapor lamp, modulated

3

1 x 1 foot gasoline

100

7.1

300 w incandescent lamp, modulated

3

1 x 1 foot gasoline

100

9.6

500 w unshielded quartz halogen lamp, modulated

8

1 x 1 foot gasoline

100

6.3

1500 w electric radiant heater, modulated

10

1 x 1 foot gasoline

90

6.4

Two 34 w fluorescent lamps, modulated

3

1 x 1 foot gasoline

100

4.6

Medium Sensitivity

* Fire was verified with very high sensitivity only.

Advertising