Det-Tronics X3300EXE Protect-IR Multispectrum IR Flame Detector User Manual
Page 18
![background image](/manuals/557725/18/background.png)
16
X3300 Response Characteristics (0.5 Sec. Response Only)
Medium Sensitivity
Fuel
Size
Distance
Ave. Response Time, Sec.
Ft. (M)
On Axis (0°)
Off Axis (45°)
Methanol
Atomized Fuel Fire
50
.39
.40
10 CC Per Sec.
(15)
Isopropanol
Atomized Fuel Fire
50
.39
.40
10 CC Per Sec.
(15)
Acetone
Atomized Fuel Fire
50
.36
.38
10 CC Per Sec.
(15)
Heptane
Atomized Fuel Fire
50
.39
.40
10 CC Per Sec.
(15)
RESPONSE CHARACTERISTICS — AUTOMOTIVE APPLICATIONS:
X3300 Response Characteristics
Medium Sensitivity
Fuel
Size
Distance
Ave. Response Time, Sec.
Ft. (M)
On Axis (0°)
Off Axis (45°)
Methanol
36 Sq. In.
20
6.9
9.9
(0.023 Sq. M.)
(6)
Isopropanol
36 Sq. In.
35
3.3
7.3
(0.023 Sq. M.)
(10.5)
Heptane
36 Sq. In.
40
2.6
8.6
(0.023 Sq. M.)
(12)
NOTE: Atomized fuel fires of methanol, isopropanol, acetone and heptane
are detectable within 0.5 second at a distance of 50 feet. Fuel
flow rate equals 10 cc per second.