X3300 Response Characteristics (0.5 Sec. Response Only)

Medium Sensitivity

Fuel

Size

Distance

Ave. Response Time, Sec.

Ft. (M)

On Axis (0°)

Off Axis (45°)

Methanol

Atomized Fuel Fire

50

.39

.40

10 CC Per Sec.

(15)

Isopropanol

Atomized Fuel Fire

50

.39

.40

10 CC Per Sec.

(15)

Acetone

Atomized Fuel Fire

50

.36

.38

10 CC Per Sec.

(15)

Heptane

Atomized Fuel Fire

50

.39

.40

10 CC Per Sec.

(15)

RESPONSE CHARACTERISTICS — AUTOMOTIVE APPLICATIONS: