Operating Instructions AR Evaluation Unit CES-AR-AES-12

10

Starting behavior

The AR evaluation unit can be placed in operation either using the autostart mode 

or by starting it manually. 

Important!

If the configuration for the starting behavior is changed during operation (e.g. 
jumper removed), this change will be detected by the unit. The AR evaluation unit 
assumes the fault state as soon as the next request to close the safety contacts 
is received (see section Troubleshooting).

Connection for monitored, manual start

For a monitored, manual start, a start button is connected to terminal S. The start 

button is supplied with a voltage of 24 V DC. The terminal +UB can be used for this 

purpose. A sticking start button, for example, will be detected by the monitoring 

function the next time the system is powered up.
The safety contacts close after max. 600 ms when the start button is pressed and 

then released again (falling edge) and if the actuators for all the safety switches 

connected are within the operating distance.

CES-AR-AES

UB

S

Fig. 4: Monitored, manual start

Important!

The start button is only allowed to be pressed approx. 8 s after power on. If the 
start button is pressed earlier, the unit will switch to the fault state and the LED 
DIA illuminates. The LED STATE flashes 

(see section Troubleshooting)

. 

Connection for automatic start

Warning!

The safety contacts close immediately if all safety switches signal a safe state 
and the feedback loop is closed.

CES-AR-AES

Y1

S

Fig. 5: Automatic start