Dimension drawing system times for the ar system, Typical system times – EUCHNER CES-AR-AES-12 User Manual

Page 19

Advertising
background image

Operating Instructions AR Evaluation Unit CES-AR-AES-12

19

Dimension drawing

System times for the AR system

Typical system times

Ready delay: After switching on, the unit carries out a self-test for 8 s. The system 

is ready for operation only after this time.
Risk time according to EN 60947-5-3: If an actuator leaves the operating 

distance, the safety contacts on the AR evaluation unit are opened at the latest 

after 520 ms. 
Difference time: The safety contacts on the AR evaluation unit switch with a 
slight time offset. They have the same signal state at the latest after a difference 
time of 10 ms.

Important!

The system times shown are maximum values for a circuit arrangement with 
12 safety switches connected in an AR switch chain. Shorter times can also be 
achieved in circuits with fewer switches.

t

0

t

0

t

0

=

=

+ 520 ms

t

off

t

0

+ 450 ms

t

off

t

off

t

0

= + 750 ms

t

off

Normal operation

Fault detection

Short circuit on IA/IB

Actuator removal

or deactivating of

a guard locking

Non-identical input state

on IA/IB or short circuit

on IA or IB

or internal fault

t (ms)

= Safety outputs active
= Switch-off time

= Fault time/event

Fig. 9: System times for AR evaluation unit on an AR switch chain with 12 safety

switches

45

99

114

O4

O12

O3

O11

O2

O10

O1
O9

+UB
+UB

0V

S

DIA

Y2

Y1

43
44

33
34

23
24

13
14

CES-AR

EUCHNER

Safety Unit

O5

IA

O6

IB

O7

RESET

DIA OUT STATE

O8

0V

AR

UB

AR

OUT

AR

Suitable for DIN rail 
according to DIN 60715