Setup – EUCHNER CES-AR-AES-12 User Manual

Page 15

Advertising
background image

Operating Instructions AR Evaluation Unit CES-AR-AES-12

15

Setup

Warning!

 Ì

Pay attention to the notes on commissioning and on the teach-in process in 
the operating instructions for the safety switch used.

 Ì

In case of devices with teach-in input, ensure the circuit is correct.

Proceed as follows:
1.  Ensure nobody can be placed in danger during setup.
2.  Prior to setup, check whether all connections are correct (jumpers connected, 

external circuit correct) and the AR switch chain is fitted with a bridging plug.

3.  Close all safety guards and make sure that the feedback loop on the evaluation 

unit is closed. 

4.  Switch on the power supply.

¨

The switches in the chain are initialized on starting. Unicode switches that have 

not yet taught-in an actuator on starting, automatically teach-in the actuator. 

This process can take up to one minute.

¨

If the AR evaluation unit is set up for automatic start, the OUT LED flashes and 

signals that the self-test is being performed. After the self-test, the OUT and 

STATE LEDs are continuously lit. 

or

¨

If you start the AR evaluation unit manually, the STATE LED flashes and signals 

that the self-test is being carried out. After the self-test, the STATE LED illumi-

nates continuously. The OUT LED flashes, since no start command has been 

issued yet.

5.  Press the start button (only necessary for manual start).
6.  Then press the RST button on the AR evaluation unit for approx. 3 s to re-start 

the device.

7.  Check the correct function of the safety circuits connected. In case of problems, 

see section Troubleshooting.

Important!

Use the status table in the section Troubleshooting to check the overall function. 
In addition, the status LEDs on the respective safety switches provide information 
about the status of the respective switch.

Advertising