Operating Instructions AR Evaluation Unit CES-AR-AES-12

12

If a feedback loop is not to be connected, a jumper must be fitted to the terminals 

Y1 and Y2 (see Figure 7).  

CES-AR-AES

33 43

23

13

Y2

Y1

24 34 44

14

+24 V

Subsequent

devices

(e.g. contactors)

Fig. 7: Safety contacts connected and jumper on the feedback loop

The following conditions must be met for the safety contacts to be closed:
For manual start

 Ì

The feedback loop is closed 

 Ì

The start button has been pressed and released (switches on falling edge)

 Ì

All safety doors closed

For automatic start

 Ì

The feedback loop is closed

 Ì

All safety doors closed

If the feedback loop is open, the

DIA LED flashes and the STATE LED is lit 

(see 

section Troubleshooting). The monitoring output DIA is set.

The safety contacts remain open if the feedback loop is open at the start. The unit 

switches to fault state, the DIA LED illuminates, and the STATE LED flashes (see 

section Troubleshooting).