Control input/output connections – Johnson Systems EDI-120 Control Retrofit User Manual

Page 11

Advertising
background image

www.johnsonsystems.com

11

INPUT/OUTPUT

CONTACTS

0-10VDC

ANALOG INPUTS

+12 VDC

POWER SUPPLY

2 AMPS MAXIMUM

COMMON

OVER

TEMP

INPUT

(N.O)

FIRE

ALARM (N.O)

SECURITY

ALARM (N.O)

AUXILIAR

Y INPUT

(N.O)

OPEN COLLECT

OR OUTPUT

COMMON

+ 12 VDC

ANALOG INPUT

1

ANALOG INPUT

2

ANALOG INPUT

3

ANALOG INPUT

4

COMMON

COMMON

COMMON

+ 12 VDC

+ 12 VDC

+ 12 VDC

DMX-A AND DMX-B

INPUT AND THRU

DAISY-CHAIN MULTI-

RACK INSTALLATIONS

ISOLATED DUAL DMX INPUT AND THRU

SHIELD / COMMON

DATA

-

DATA

+

SHIELD / COMMON

DATA

-

DATA

+

SHIELD / COMMON

DATA

-

DATA

+

SHIELD / COMMON

DATA

-

DATA

+

DMX-A

INPUT

DMX-A

THRU

DMX-B

INPUT

DMX-B

THRU

Control Input/Output Connections

All EDI-120 retrofit control systems come with a variety of control input and output (I/O)

capabilities. All I/O connections are terminated on the connectors located at the rear of

the EDI-120 chassis.
Breakaway type connectors are provided for all I/O connections.

• Use wire size #28 to #12 AWG.

• Strip wire insulation length to 0.28” (7mm).

• Use a 1/8” (3.2mm) flat head screwdriver to tighten connections.

• Torque connections to 3.5 IN-LBS (0.4 NM).

NOTE: For connection use copper wire only, rated for 167°F (75°C) minimum.

Isolated Dual DMX Input and Thru

• DMX-A (SHIELD/COMMON, DATA-, DATA+) input and thru is terminated on the two 3-position breakaway

connectors provided.

• DMX-B (SHIELD/COMMON, DATA-, DATA+) input and thru is terminated on the two 3-position breakaway

connectors provided.

• For multi-rack EDI-120 installations, a 10’ (3m) CAT 5e patch cable is supplied. This cable is used to daisy-

chain the DMX-A and DMX-B between systems. The CAT 5e patch cable plugs into the RJ45 connectors

located at the rear of the EDI-120 chassis.

• Complies with USITT DMX512-A (ANSI E1.11 - 2008), standard protocol for digital data control.

• Recommended cable is Belden 9829, 9842, Cat 5 or equivalent (low-capacitance, twisted pair).

• Wiring must follow a daisy-chain topology.

• Maximum of 32 receiving devices on a single DMX line.

• Maximum cable length is 1,500 feet (455 meters).

For more information, Google DMX, or visit: http://old.usitt.org/DMX512FAQ.aspx

NOTE: Ensure only the last (end-of-line) DMX receiving device is terminated! Refer to

menu items “DMXA TRM” and “DMXB TRM” on page 21 for further details.