16. DIM CURV

Configure the dimmer curve for each output.

There are four different dimmer curve profiles that can be assigned to each individual

dimmer output circuit. Square Law (SQ) curve is the industry standard and the default

for all dimmers. Linear (LN) curve modifies the dimmer output for a linear relationship

to the control input level. Direct Drive (DD) curve is not modified - meaning the control

input level is directly proportional to the control output level. Non-Dim (ND) curve

assigns the dimmer circuit to operate in a full-on or off state only, with no dimming.

Dimmers set for non-dim will be triggered full-on at 55% control input and will be

triggered off again at 45% control input.

Press EXECUTE to enter the menu.

D 001 SQ

Displays the dimmer (D) output (001) and its current dimmer curve.

D 120 SQ

Press MENU ( ) to select the desired dimmer number from 001 to 120.

D 120 LN

Press EXECUTE to toggle to linear (LN) curve mode.

D 120 DD

Press EXECUTE to toggle to direct drive (DD) mode.

D 120 ND

Press EXECUTE to toggle to non-dim (ND) mode.

Press ESCAPE to exit the menu and save the desired dimmer curves.

Press RESET to exit the menu without saving.

The menu will automatically timeout after 5 minutes of inactivity and save.

17. VOUT LIM

Set the maximum RMS output voltage for each dimmer.

Limiting the maximum RMS voltage can greatly improve lamp life.

Press EXECUTE to enter the menu.

001<127.5

Displays the dimmer (001) and its current maximum output voltage level (127.5).

120<127.5

Press MENU ( ) to select the desired dimmer number from 001 to 120.

120>127.5

Press EXECUTE to toggle the pointer (< >) to select the output voltage level.

120>100.0

Press MENU ( ) to adjust the output voltage level in 0.5 Volt increments.

120<100.0

Press EXECUTE to toggle the pointer (< >) to select another dimmer number.

Press ESCAPE to exit the menu and save the desired dimmer curves.

Press RESET to exit the menu without saving.

The menu will automatically timeout after 5 minutes of inactivity and save.

18. REGULATE

Enable or disable the dimmer output voltage regulation.

With the on-board output voltage regulation feature enabled, the maximum RMS

output is limited to 118 Volts. Voltage regulation automatically adjusts the internal

control level to compensate for any line voltage fluctuations.

ENABLED

Press EXECUTE to toggle regulation from ENABLED to DISABLED.

DISABLED

Press EXECUTE to toggle regulation from DISABLED to ENABLED.

Any change in the configuration is automatically saved.

19. ANA MODE

Configure the analog inputs for normal or load shed mode.

Each of the four (4) analog inputs can be independently configured for normal

(NORM) or load shed (SHED) mode of operation.

Normal (NORM) mode sets the analog input for 0-10VDC operation. The analog

voltage level sensed sets the level for the selected dimmer outputs.

Load shed (SHED) mode is used as a power management interface to building

management systems (BMS). Contact closure devices such as a photocell or

maintained switch contact may be used to trigger the analog input. When a voltage

of 5.5VDC to 12VDC is sensed on the analog input the selected dimmer outputs are

disabled (set to zero output level). The selected dimmer outputs are enabled when

the voltage sensed on the analog input drops to below 4.5VDC.

Press EXECUTE to enter the menu and set the mode for each analog input.

A01<NORM

Displays the active analog input (A01) and current mode setting (NORM).

A04<NORM

Press MENU ( ) to select the desired analog input to configure.

A04<SHED

Press EXECUTE to toggle from normal (NORM) to load shed (SHED) mode.

Press ESCAPE to exit the menu and save the desired analog input modes.

Press RESET to exit the menu without saving.

The menu will automatically timeout after 5 minutes of inactivity and save.