9.1 Tank Fill Controller

A mining concern has a large slurry tank with 4 load-cells mounted on each of it’s four legs. Before rock is
added, a certain amount of water must be initially present in the tank. This is can be easily accomplished
using the PLC like functionality of the DS-3000. An external trigger from the main plant process controller,
triggers the process start and tares the DS3000U, then water is added under control of the DS-3000U output
#1. Once the weight of tank + water exceeds the desired setpoint, the DS-3000 stops the water flow into the
tank.

9.1.1

Application Requirements:

1. 4x sensors each with 10000 Lb load capacity each = 40000 Lb total scale load capacity

2. Typical empty tank “dead” weight, with no water or minerals present: 1200 Lbs.

3. Acceptable tank trigger “filled with water” weight: 3500 lbs.

4. Let Sensor 1 – Sensor 4 correspond to the four load-cells, each corresponds to one DS-3000

module input.

9.1.2

Implementation Details:

1. Connect the “water control valve” to Output #1, so when the relay is active, water flows into the

tank.

2. Connect each of the four load-cells to consecutive inputs on the DS-3000.

3. Connect the process controller start contacts to the “remote” input on the DS-3000.

4. Assume units of pounds (Lbs), make sure the front panel LED is illuminated in the Lbs position.