Loadstar Sensors DS-3000 Digital Load Cell Display & Controller User Manual

Page 29

Advertising
background image

DS-3000U

DS3000 User Guide

Loadstar Sensors, Inc.

Page: 29 / 48

033-01419 Rev. 4

Figure 9: Wiring for Program Example 1

9.1.3

Programming Summary

1. Configure the DS-3000 remote input to “reset” and “tare” the displayed value at program start.

“Reset” means, output #1 will be reset to it’s default state, and will remain there until triggered.
“Tare” means to automatically zero the results at whatever the current load value is.

2. Set the threshold to activate relay #1 at below the tare value say -10 lbs

3. Set the threshold to de-activate relay #1 at the desired cut-off weight: 3500 – 1200 = 2300 lbs.

4. Keep the output turned off, until the system resets the whole process and water is actually

desired to flow into the tank.

9.1.4

Programming the DS-3000:

1. Press

and

hold

menu

until “Enter Pass” and “000000” appear on the display

2. Press

the

up

or down keys to select the programming mode password (default is 000001)

3. Press

enter

4. You are now in programming mode at the dsplay prompt. Press mode until you reach the

relay 1 menu.

5. Press

down

, to the trgr1 entry. Press enter, and a numeric entry field will appear. Enter the

initial trigger weight of -10 Lb. Press menu until the digit corresponding to the 1 is highlighted,
then press up and down to set the digit to 1. Press mode again to highlight each digit in turn,
then up and down to set each one to the correct value.

6. Press

enter

when you are complete. Press down to get to the next programming entry.