Static p ressur e (in. w g), Perfect humidity coil – Bryant LEGACY 580J User Manual

Page 32

Advertising
background image

32

Table 17 – STATIC PRESSURE ADDERS (in. wg) -- Factory Options and/or Accessories

Perfect Humidity

0.00

0.02

0.04

0.06

0.08

0.10

0.12

0.14

0.16

0.18

0.20

4000

5000

6000

7000

8000

9000 10000 11000 12000 13000

CFM Air Flow

Static P

ressur

e (in. w

g)

Perfect Humidity Coil

558J/580J17-20

558J/580J 24

558J/580J 28

C11175B

Economizer -- Vertical and Horizontal Duct Configuration

MODEL SIZES 17 --- 28

CFM

4500

5000

5500

6000

6500

7000

7500

8000

Pressure Adders (in. wg)

0.047

0.052

0.057

0.062

0.067

0.072

0.077

0.082

MODEL SIZES 17 --- 28

CFM

8500

9000

9500

10000

10500

11000

11500

12000

12500

Pressure Adders (in. wg)

0.088

0.093

0.098

0.103

0.109

0.114

0.119

0.125

0.131

580J