Bryant LEGACY 580J User Manual

Page 54

Advertising
background image

54

15. High Efficient Motors listed shall meet section 313 of the Energy Independence and Security Act of 2007 (EISA

2007).

23 81 19.13.C. Delivery, Storage, and Handling

1. Unit shall be stored and handled per manufacturer’s recommendations.
2. Lifted by crane requires either shipping top panel or spreader bars.
3. Unit shall only be stored or positioned in the upright position.

23 81 19.13.E.

Project Conditions

1. As specified in the contract.

23 81 19.13.F.

Operating Characteristics

1. Unit shall be capable of starting and running at 115_F (46_C) ambient outdoor temperature, meeting maximum

load criteria of AHRI Standard 340/360 at ± 10% voltage.

2. Compressor with standard controls shall be capable of operation down to 30_F (--1_C), ambient outdoor temperat-

ures. Accessory winter start kit is necessary if mechanically cooling at ambient temperatures below 30_F (--1_C).

3. Unit shall discharge supply air vertically or horizontally as shown on contract drawings.
4. Unit shall be factory configured and ordered for vertical supply & return configurations.
5. Unit shall be factory furnished for either vertical or horizontal configuration without the use of special conversion

kits. No field conversion is possible.

23 81 19.13.G. Electrical Requirements

1. Main power supply voltage, phase, and frequency must match those required by the manufacturer.

23 81 19.13.H. Unit Cabinet

1. Unit cabinet shall be constructed of galvanized steel, and shall be bonderized and coated with a pre--painted baked

enamel finish on all externally exposed surfaces.

2. Unit cabinet exterior paint shall be: film thickness, (dry) 0.003 inches minimum, gloss (per ASTM D523, 60_F /

16_C): 60, Hardness: H--2H Pencil hardness.

3. Evaporator fan compartment interior cabinet insulation shall conform to AHRI Standard 340/360 minimum exteri-

or sweat criteria. Interior surfaces shall be insulated with a minimum 1/2--in. thick, 1 lb density, flexible fiberglass

insulation, neoprene coated on the air side. Aluminum foil--faced fiberglass insulation shall be used in the gas heat

compartment.

4. Base of unit shall have a minimum of four locations for thru--the--base gas and electrical connections standard.

Both gas and electric connections shall be internal to the cabinet to protect from environmental issues.

5. Base Rail

a. Unit shall have base rails on a minimum of 2 sides.

b. Holes shall be provided in the base rails for rigging shackles to facilitate maneuvering and overhead rigging.

c. Holes shall be provided in the base rail for moving the rooftop by fork truck.

d. Base rail shall be a minimum of 16 gauge thickness.

6. Condensate pan and connections:

a. Shall be a sloped condensate drain pan made of a non--corrosive material.

b. Shall comply with ASHRAE Standard 62.

c. Shall use a 3/4--in --14 NPT drain connection, through the side of the drain pan. Connection shall be made per

manufacturer’s recommendations.

7. Top panel:

a. Shall be a multi--piece top panel linked with water tight flanges and locking systems.

8. Gas Connections:

a. All gas piping connecting to unit gas valve shall enter the unit cabinet at a single location on side of unit (ho-

rizontal plane).

b. Thru--the--base capability

(1.) Standard unit shall have a thru--the--base gas--line location using a raised, embossed portion of the unit

basepan.

(2.) Optional, factory--approved, water--tight connection method must be used for thru--the--base gas connec-

tions.

(3.) No basepan penetration, other than those authorized by the manufacturer, is permitted.

9. Electrical Connections

a. All unit power wiring shall enter unit cabinet at a single, factory--prepared, knockout location.

b. Thru--the--base capability.

580J

Advertising